2 Installation
32
© Copyright Reserved Autonics Co., Ltd.
2.2
Power Wiring
For power supply, use the wire of which cross section is at least 0.75mm² and use the wire
of which cross section is at least 1.25mm² for grounding.
Use round terminal with at least 3mm of internal diameter and less than 6mm of external
diameter.
Do not apply power before power line connection.
Check power polarity.
Tighten the terminal screw with 0.5 to 0.8N·m torque
Ground resistance should be less than 100Ω and ground it separately.
Caution for power wiring
Before connecting power line, must check power polarity.
Do not connect the power when the power is supplied.
Observe following allowable voltage change range of power voltage.
Power voltage
24VDC
Allowable voltage change range
21.6 to 26.4VDC
When connecting power, supply power with the power supply which has inner protection
circuit. If the power supply which does not have inner protection circuit is used, protection
circuits such as fuse must be installed before using this.
Summary of Contents for LP-A Series
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 27: ...1 Overview Copyright Reserved Autonics Co Ltd 27 1 8 Dimension 1 8 1 LP A070 unit mm ...
Page 28: ...1 Overview 28 Copyright Reserved Autonics Co Ltd 1 8 2 LP A104 unit mm ...
Page 29: ...1 Overview Copyright Reserved Autonics Co Ltd 29 1 8 3 Common ...
Page 30: ...1 Overview 30 Copyright Reserved Autonics Co Ltd ...
Page 38: ...2 Installation 38 Copyright Reserved Autonics Co Ltd ...
Page 46: ...3 System Organization 46 Copyright Reserved Autonics Co Ltd ...
Page 66: ...6 Troubleshooting 66 Copyright Reserved Autonics Co Ltd ...
Page 70: ...7 Repair Maintenance Inspection 70 Copyright Reserved Autonics Co Ltd ...
Page 105: ...9 Appendix Copyright Reserved Autonics Co Ltd 105 ...