Line
Function
Setting range or display
Setting
increment
Basic setting
DHW setting (domestic hot water)
1610
U
Comfort setting
Reduced value (line 1612)…
65 °C
1
55 °C
1612
U
Reduced setting
8 °C...
Comfort value (line 1610)
1
40 °C
1620
I
Release of DHW load
24h / day
Heating circuit time programme
Programme 4 / DHW
Off-peak tariff (Off-peak)
Programme 4 / DHW
and Off-peak
Heating
circuit timer
prog .
24h / day
: The temperature of the DHW is constantly maintained at the DHW comfort setting.
Heating circuit time programme:
The DHW is produced according to the programming for the ambient temperature
(with 1 hour in advance when switched on).
Programme 4 / DHW:
The DHW programme is separate form the heating circuit programme.
Off-peak tariff (THC)
: Not concerned
T'prog 4/DHW or low-tariff
: Not concerned
1640
I
Anti-legionnella function
Off,
Periodic (depending line setting 1641)
Set day of the week (depending
line setting 1642)
Off
1641
S
Intervals for the anti-legionella cycles
1 to 7
1 day
7
1642
S
Weekday anti-legionella cycle run
Monday, Tuesday,...
Saturday
1644
S
Legionella funct time
00:00... 23:50
10 min
---
1645
S
Legionella funct setpoint
55... 95 °C
1 °C
60 °C
1646
S
Legionella funct duration
0... 360 min
1 min
60 min
1647
S
Legionella funct circ pump
Off, On
Off
1660
S
Circulating pump release
Time switch program HC/CC 3,
DHW release,
Time switch program 4/DHW,
Time switch program 5
DHW release
Heat pump (HP)
2803
S
Overrun time cond pump
8... 240 s
1 s
240s
2843
S
Compressor off time min
0... 120 min
1 min
8 min
2844
S
Switch-off temp max
8... 100 °C
1 °C
65 °C
2862
S
Locking time stage 2
0... 40 min
1 min
5 min
2873
S
Compressor mod run time
10... 600 s
1 s
240 s
2882
S
Release integr electric flow
0... 500 °Cmin
1 °Cmin
100 °Cmin
2884
S
Release el flow below OT
Electrical release - start-up with outside
temperature
-30... 30 °C
2 °C
2903
I
Release strategy
COP, Energy price
Energy price
2916
S
Max setpoint HP DHW charg
8... 80 °C
52 °C
2920
S
With electrical utility lock (EX1)
Locked (Blocked on standby),
Released
Blocked while
waiting
Liberated
: Heat pump = start _ boiler = start.
Blocked while waiting (Locked)
Heat pump = stop _ boiler = start.
Energy meter
3095
S
Not used
3267
U
*
These menus may not appear. They depend on the appliance's configuration.
Installation and commissioning instructions "1485 - EN"
- 61 -
Heat pump alféa hybrid duo gas
Summary of Contents for WOYG112LHT
Page 51: ... Installation and commissioning instructions 1485 EN 51 Heat pump alféa hybrid duo gas ...
Page 69: ... Installation and commissioning instructions 1485 EN 69 Heat pump alféa hybrid duo gas ...
Page 90: ...Installation and commissioning instructions 1485 EN Heat pump alféa hybrid duo gas 90 ...
Page 91: ...Installation and commissioning instructions 1485 EN 91 Heat pump alféa hybrid duo gas ...