figure 26 - Refrigerating link connection (accepted diameters and lengths)
"Gas" refrigerating connection
diameter D1
"Liquid" refrigerating connection
diameter D2
Flare nut
Flare nut
Flare
nut
Flare
nut
"Liquid"
valve
"Gas"
valve
Hydraulic
module
Outdoor
unit
D
L
Heat pump
Hydraulic
module
Heat pump
Outdoor unit
Heat pump model
alféa hybrid gas single phase / three phase
gas
liquid
Raccords unité extérieure
5/8"
3/8"
Liaisons frigorifiques
Diameter
(D1) 5/8"
(D2) 3/8"
Minimum length
(L)
5
Maximum length
(L)
15 * / 20 **
Difference in height
(D)
15 * / 20 **
Hydraulic module connectors
5/8"
3/8"
*
: without additional charge of R410A
** : Taking into account the potential additional charge of refrigerating fluid R410A (see §
).
Installation and commissioning instructions "1485 - EN"
- 27 -
Heat pump alféa hybrid duo gas