Line
Function
Setting range or display
Setting
increment
Basic setting
741
I
Flow temp setpoint max
Flow temp setpoint min... 70 °C
1 °C
55 °C
Underfloor heating (compulsory with 2 circuit kit) = 50 °C / Radiators = 65 °C.
Important note:
The maximum limit is not a safety function as that required for under-floor heating.
750
S
Influence of the ambient temperature
1%... 100%
1%
50%
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
760
S
Room temperature limitation
0,5... 4 °C
0.5 °C
0.5 °C
As soon as the room temperature = [Setpoint line
710
(ex. 20°C) + Room temperature limitation setpoint line
760
(ex. 0,5 °C)] > 20,5 °C => The heat pump is stopped.
It restarts when the room temperature falls below the setpoint (in the example, Room temperature < 20,0 °C).
780
S
Quick setback
Off, Down to reduced setpoint,
Down to frost prot setpoint
Off
790
S
Maximum optimisation on switch-on
(Early start to switch to the comfort setting.)
0... 360 min
10 min
180 min
791
S
Maximum optimisation on switch-off (Early stop to
switch from the comfort setting to the reduced setting.)
0...360 min
10 min
30 min
800
S
Start of increase in reduced functioning mode
-30... 10 °C
1 °C
--
801
S
End of increase in reduced functioning mode
-30... 10 °C
1 °C
-5 °C
830
S
Mixer valve boost
0... 50 °C
1 °C
0 °C
834
S
Servomotor travel time
30... 873 s
1 s
240 s
850
I
Floor controlled drying (
Off
- Off: Early interruption of the current programme, programme inactive.
- Operational heating
- Heating ready for occupation.
- Operational h ready heating.
- Ready h operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends
automatically after 25 days.
851
I
Manual floor drying setpoint
(if line 850 = manual)
0... 95 °C
1 °C
25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed.
The concrete slab-drying programme stops automatically after running for 25 days.
856
I
Current drying day
0... 32
0
857
I
Terminated drying days
0... 32
0
900
S
Change of regime
None, Protection mode,
Reduced, Comfort, Automatic
1
Reduced
Operating mode at end of concrete slab drying period
"
Please comply with the
standards and instructions
of the manufacturer of
the building ! A good
performance of this function
is only possible with an
installation correctly
implemented
(hydraulic,
electricity and adjustments) !
This function can be stopped
by anticipation when setting
the adjustment on "Off".
50
45
40
35
30
20
5
0
25
55
1
1
5
7
X
10
18
25
15
1
figure 59 - Diagram of the concrete slab drying programmes
Heating flow temperature °C
Operational h Heating ready for occupation
Heating ready for occupation
Day
Operational
heating
Installation and commissioning instructions "1485 - EN"
- 59 -
Heat pump alféa hybrid duo gas
Summary of Contents for WOYG112LHT
Page 51: ... Installation and commissioning instructions 1485 EN 51 Heat pump alféa hybrid duo gas ...
Page 69: ... Installation and commissioning instructions 1485 EN 69 Heat pump alféa hybrid duo gas ...
Page 90: ...Installation and commissioning instructions 1485 EN Heat pump alféa hybrid duo gas 90 ...
Page 91: ...Installation and commissioning instructions 1485 EN 91 Heat pump alféa hybrid duo gas ...