AL3 group - Alarm 3 parameters
no. Param.
Description
Dec.
Point
Values
Default
41
AL3t
Alarm 3 type
0
nonE
Alarm not used;
LoAb
Absolute low alarm;
HiAb
Absolute high alarm;
LHAo
Windows alarm in alarm outside the windows;
LHAi
Windows alarm in alarm inside the windows;
SE.br
Sensor Break;
LodE
Deviation low alarm (relative);
HidE
Deviation high alarm (relative);
LHdo
Relative band alarm in alarm out of the band;
LHdi
Relative band alarm in alarm inside the band.
nonE
42
Ab3
Alarm 3 function
0
0... 15:
+1 Not active at Power ON;
+2 Latched alarm (manual reset);
+4 Acknowledgeable alarm;
+8 Relative alarm not active at Set Point change.
0
43
AL3L
For band alarm, it is low alarm threshold
dp
From -1999 to AL3H (E.U.)
-1999
44
AL3H
For band alarm, it is high alarm threshold
dp
From AL3L to 9999 (E.U.)
9999
45
AL3
AL3 threshold
dp
From AL3L to AL3H (E.U.)
0
46
HAL3
AL3 hysteresis
dp
1... 9999 (E.U.)
1
47
AL3d
AL3 delay
0
0
oFF (disable)
1... 9999 (s)
oFF
48
AL3o
Alarm 3 enabling during Stand-by mode and
in over or under range conditions
0
0 Alarm 1 disabled during Stand by and out of range
conditions;
1 Alarm 1 enabled in stand by mode;
2 Alarm 1 enabled in out of range conditions;
3 Alarm 1 enabled in stand by mode and out of range
conditions.
0
]
HBD group - Heater Break Down Parameters
no. Param.
Description
Dec.
Point
Values
Default
49
Ct.So
Current Transformer signal source
0
OFF
HBD not used;
nonE
Asynchronous amperometer;
out3
Synchronous to Out 3;
out2
Synchronous to Out 2;
out1
Synchronous to Out 1.
oFF
50
Ct.dF
Current measure decimal point
0
0, 1 or 2
10
51
Ct.rA
CT end of scale
Ct.dF 1... 999 (A)
20
52
Ct.FL
Filter on the CT measure
0
no
Filter disabled;
YES
Filter enabled.
no
53
Ct.LA
HBD alarm function
0
0
Automatic reset;
1
Manual reset;
2
Acknowledgeable alarm.
54
Ct.Ld
CT threshold with output ON
Ct.dF oFF
Threshold disabled (inhibited);
1... 999 (A)
55
Ct.LE
CT threshold with output oFF (leakage)
Ct.dF oFF
Threshold disabled (inhibited);
1... 999 (A)
56
Ct.oc
Overcurrent
Ct.dF oFF
Threshold disabled (inhibited);
1... 999 (A)
]
rEG group - Control Parameters
no. Param.
Description
Dec.
Point
Values
Default
57
cont
Control type when at least one
heating output and one cooling
output are configured
0
Pid
PID control;
nr
ON/OFF control with neutral zone.
Pid
Control type when the outputs are
configured for heating or cooling
0
Pid
PID (heat and/or);
On.FA ON/OFF asymmetric hysteresis;
On.FS ON/OFF symmetric hysteresis.