no. Param.
Description
Dec.
Point
Values
Default
126
dSPu
Instrument status at power
ON
0
AS.Pr
Starts in the same way it was prior to the power down;
Auto
Starts in Auto mode;
oP.0
Starts in manual mode with a power output equal to zero;
St.bY
Starts in stand-by mode.
AS.Pr
127
oPr.E
Operative modes enabling 0
ALL
All modes will be selectable by the next parameter;
Au.oP Auto and manual (oPLo) mode only will be selectable by the next
parameter;
Au.Sb
Auto and Stand-by modes only will be selectable by the next parameter
ALL
128
oPEr
Operative mode selection
Auto
Auto mode;
oPLo
Manual mode;
St.bY
Stand by mode.
Auto
]
Ser group - Serial link parameters
no. Param.
Description
Dec.
Point
Values
Default
129
Add
Instrument address
- oFF;
- 1... 254.
1
130
bAud
baud rate
1200
1200 baud;
2400
2400 baud;
9600
9600 baud;
19.2 19200 baud;
38.4 38400 baud.
9600
131
trSP
Selection of the value to
be retransmitted (Master)
nonE Retransmission not used (the instrument is a slave);
rSP
The instrument retransmits the operative Set Point;
PErc The instrument retransmits the power output percentage
nonE
]
COn group - Consumption parameters
no. Param.
Description
Dec.
Point
Values
Default
132
Co.tY
Count type
0
oFF Not used;
1 Instantaneous power (kW);
2 Power consumption (kW/h);
3 Energy used during program execution. This measure starts from
zero when a program runs end stops at the end of the program. A
new program execution will reset the value;
4 Total worked days: number of hours the instrument is turned ON
divided by 24;
5 Total worked hours: number of hours that the instrument is turned ON;
6 Total worked days with threshold: number of hours the instrument is
turned ON divided by 24, the controller is forced in stand-by when
Co.ty value reaches the threshold set in [135] h.Job;
7 Total worked hours with threshold: number of hours that the instru-
ment is turned ON, the controller is forced in stand-by when Co.ty
value reaches the threshold set in [135] h.Job;
8 Totalizer of control relay worked days: number of hours the control
relay has been in ON condition, divided by 24;
9 Totalizer of control relay worked hours: number of hours the control
relay has been in ON condition;
10 Totalizer of control relay worked days with threshold: number of
hours the control relay has been in ON condition divided by 24,
the controller is forced in stand-by when Co.ty value reaches the
threshold set in [135] h.Job;
11 Totalizer of control relay worked hours with threshold: number of hours
the control relay has been in ON condition, the controller is forced in
stand-by when Co.ty value reaches the threshold set in [135] h.Job.
oFF
133
UoLt
Nominal Voltage of the load
0
1... 9999 (V)
230
134
cur
Nominal current of the load
0
1... 999 (A)
10
135
h.Job
Threshold of the working
hours
0
oFF Threshold not used;
0... 9999 hours.
0
136
t.Job
Worked days (not resettable) 0
0... 9999 days