Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL -
PAG. 32
]
AL1 group - Alarm 1 parameters
no. Param.
Description
Dec.
Point
Values
Default
25
AL1t
Alarm 1 type
0
nonE
Alarm not used;
LoAb
Absolute low alarm;
HiAb
Absolute high alarm;
LHAo
Windows alarm in alarm outside the windows;
LHAi
Windows alarm in alarm inside the windows;
SE.br
Sensor Break;
LodE
Deviation low alarm (relative);
HidE
Deviation high alarm (relative);
LHdo
Relative band alarm in alarm out of the band;
LHdi
Relative band alarm in alarm inside the band.
HiAb
26
Ab1
Alarm 1 function
0
0... 15:
+1 Not active at Power ON;
+2 Latched alarm (manual reset);
+4 Acknowledgeable alarm;
+8 Relative alarm not active at Set Point change.
0
27
AL1L
For band alarm, it is low alarm threshold
dp
From -1999 to AL1H (E.U.)
-1999
28
AL1H
For band alarm, it is high alarm threshold
dp
From AL1L to 9999 (E.U.)
9999
29
AL1
AL1 threshold
dp
From AL1L to AL1H (E.U.)
0
30
HAL1
AL1 hysteresis
dp
1... 9999 (E.U.)
1
31
AL1d
AL1 delay
0
0
oFF (no delay)
1... 9999 (s)
oFF
32
AL1o
Alarm 1 enabling during Stand-by mode and
in over or under range conditions
0
0 Alarm 1 disabled during Stand by and out of range
conditions;
1 Alarm 1 enabled in stand by mode;
2 Alarm 1 enabled in out of range conditions;
3 Alarm 1 enabled in stand by mode and out of range
conditions.
0
]
AL2 group - Alarm 2 parameters
no. Param.
Description
Dec.
Point
Values
Default
33
AL2t
Alarm 2 type
0
nonE
Alarm disabled;
LoAb
Absolute low alarm;
HiAb
Absolute high alarm;
LHAo
Windows alarm in alarm outside the windows;
LHAi
Windows alarm in alarm inside the windows;
SE.br
Sensor Break;
LodE
Deviation low alarm (relative);
HidE
Deviation high alarm (relative);
LHdo
Relative band alarm in alarm out of the band;
LHdi
Relative band alarm in alarm inside the band.
Loab
34
Ab2
Alarm 2 function
0
0... 15:
+1 Not active at Power ON;
+2 Latched alarm (manual reset);
+4 Acknowledgeable alarm;
+8 Relative alarm not active at Set Point change
0
35
AL2L
For band alarm, it is low alarm threshold
dp
From -1999 to AL2H (E.U.)
-1999
36
AL2H
For band alarm, it is high alarm threshold
dp
From AL2L to 9999 (E.U.)
9999
37
AL2
AL2 threshold
dp
From AL2L to AL2H (E.U.)
0
38
HAL2
AL2 hysteresis
dp
1... 9999 (E.U.)
1
39
AL2d
AL2 delay
0
0
oFF (no delay)
1... 9999 (s)
oFF
40
AL2o
Alarm 2 enabling during Stand-by mode and
in over or under range conditions
0
0 Alarm 2 disabled during Stand by and out of range
conditions;
1 Alarm 2 enabled in stand by mode;
2 Alarm 2 enabled in out of range conditions;
3 Alarm 2 enabled in stand by mode and out of range
conditions.
0