Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL -
PAG. 31
no. Param.
Description
Dec.
Point
Values
Default
19
o2F
Out 2 function
0
NonE
Output not used;
H.rEG Heating output;
c.rEG
Cooling output;
AL
Alarm output;
t.out
Timer output;
t.HoF
Timer out -OFF in hold;
P.End
Program end indicator;
P.HLd
Program hold indicator;
P.uit
Program wait indicator;
P.run
Program run indicator;
P.Et1
Program Event 1;
P.Et2
Program Event 2;
or.bo
Out-of-range or burn out indicator;
P.FAL
Power failure indicator;
bo.PF
Out-of-range, burn out and Power failure indicator;
St.bY
Stand by status indicator;
diF.1
The output repeats the digital input 1 status;
diF.2
The output repeats the digital input 2 status;
on
Out 2 always ON;
riSP
Inspection request.
AL
20
o2AL
Alarms linked up with the out 2
0
0... 63:
+1 Alarm 1;
+2 Alarm 2;
+4 Alarm 3;
+8 Heater Break Down;
+16 Sensor Break;
+32 Overload on output 3.
AL1
21
o2Ac
Out 2 action
0
dir
Direct action;
rEU
Reverse action;
dir.r
Direct with reversed LED;
ReU.r
Reverse with reversed LED.
dir
22
o3F
Out 3 function
0
NonE
Output not used;
H.rEG Heating output;
c.rEG
Cooling output;
AL
Alarm output;
t.out
Timer output;
t.HoF
Timer out -OFF in hold;
P.End
Program end indicator;
P.HLd
Program hold indicator;
P.uit
Program wait indicator;
P.run
Program run indicator;
P.Et1
Program Event 1;
P.Et2
Program Event 2;
or.bo
Out-of-range or burn out indicator;
P.FAL
Power failure indicator;
bo.PF
Out-of-range, burn out and Power failure indicator;
St.bY
Stand by status indicator.
AL
23
o3AL
Alarms linked up with the out 3
0
0... 63:
+1 Alarm 1;
+2 Alarm 2;
+4 Alarm 3;
+8 Heater Break Down;
+16 Sensor Break;
+32 Overload on output 3.
AL2
24
o3Ac
Out 3 action
0
dir
Direct action;
rEU
Reverse action;
dir.r
Direct with reversed LED;
ReU.r
Reverse with reversed LED.
dir