Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 12
[36] AL2H - For High and low alarms, it is the high
limit of the AL2 threshold
-
For band alarm, it is high alarm threshold
Available:
When [33] AL2t is different from
nonE
or
[33] AL2t is different from
SE.br
.
Range:
From
[35] AL2L
to
9999
engineering units.
[37] AL2 - Alarm 2 threshold
Available:
When:
[33] AL2t = LoAb Absolute low alarm;
[33] AL2t = HiAb Absolute high alarm;
[33] AL2t = LodE Deviation low alarm (relative);
[33] AL2t = LidE Deviation high alarm (relative).
Range:
From
[35] AL2L
to
[36] AL2H
engineering units.
[38] HAL2 - Alarm 2 hysteresis
Available:
When [33] AL2t is different to
nonE
or [33] AL2t
is different from
SE.br
.
Range: 1... 9999
engineering units.
Note:
For other details see [30] HAL1 parameter.
[39] AL2d - Alarm 2 delay
Available:
When [33] AL2t different from
nonE
.
Range: 0
oFF;
1... 9999
seconds.
Note:
The alarm goes ON only when the alarm condition
persist for a time longer than [39] AL2d time but the
reset is immediate.
[40] AL2o - Alarm 2 enabling during Stand-by mode
and out of range indications
Available:
When [33] AL2t different from
nonE
.
Range: 0
Never;
1
During stand by;
2
During overrange and underrange;
3
During overrange, underrange and stand-by.
]
AL3 Group - Alarm 3 parameters
[41] AL3t - Alarm 3 type
Available:
Always.
Range: •
When one or more outputs are programmed as
control output:
nonE
Alarm not used;
LoAb
Absolute low alarm;
HiAb
Absolute high alarm;
LHAo
Absolute band alarm with alarm indication
out of the band;
LHAi
Absolute band alarm with alarm indication
inside the band;
SE.br
Sensor break;
LodE
Deviation low alarm (relative);
HidE
Deviation high alarm (relative);
LHdo
Relative band alarm with alarm indication
out of the band;
LHdi
Relative band alarm with alarm indication
inside the band;
•
When no output is programmed as control output;
nonE
Alarm not used;
LoAb
Absolute low alarm;
HiAb
Absolute high alarm;
LHAo
Absolute band alarm with alarm indication
out of the band;
LHAi
Absolute band alarm with alarm indication
inside the band;
SE.br
Sensor break.
Note:
The relative alarm are “relative” to the current Set
Point (this may be different to the Target Set Point if
you are using the ramp to Set Point function).
[42] Ab3 - Alarm 3 function
Available:
When [41] AL3t is different from
nonE
.
Range:
0... 15 with the following rule:
+1
Not active at Power ON;
+2
Latched alarm (manual reset);
+4
Acknowledgeable alarm;
+8
Relative alarm not active at Set Point change.
Example:
Setting Ad3 equal to 5 (1+4) the alarm 3 will be
“Not active at Power ON” and “Acknowledgeable”.
Note:
For other details see [26] Ab1 parameter.
[43] AL3L - For High and low alarms, it is the low
limit of the AL3 threshold
- For band alarm, it is low alarm threshold
Available:
When [41] AL3t is different from
nonE
or
[41] AL3t is different from
SE.br
.
Range: -1999
to
[44] AL3H
engineering units.
[44] AL3H - For High and low alarms, it is the high
limit of the AL3 threshold
- For band alarm, it is high alarm threshold
Available:
When [41] AL3t is different from
nonE
or
[41] AL3t is different from
SE.br
.
Range:
From
[43] AL3L
to
9999
engineering units.
[45] AL3 - Alarm 3 threshold
Available:
When:
•
[41] AL3t = LoAb Absolute low alarm;
•
[41] AL3t = HiAb Absolute high alarm;
•
[41] AL3t = LodE Deviation low alarm (relative);
•
[41] AL3t = LidE Deviation high alarm (relative).
Range:
From
[43] AL3L
to
[44] AL3H
engineering units.
[46] HAL3 - Alarm 3 hysteresis
Available:
When [41] AL3t is different from
nonE
or
[41] AL3t is different from
SE.br
.
Range: 1... 9999
engineering units.
Note:
For other details see [30] HAL1 parameter.
[47] AL3d - Alarm 3 delay
Available:
When [41] AL3t different from
nonE
.
Range: 0
oFF;
1... 9999
seconds.
Note:
The alarm goes ON only when the alarm condition
persist for a time longer than [47] AL3d time but the
reset is immediate.
[48] AL3o - Alarm 3 enabling during Stand-by mode
and out of range indications
Available:
When [41] AL3t is different from
nonE
or
[41] AL3t is different from
SE.br
.
Range: 0
Never;
1
During stand by;
2
During overrange and underrange;
3