![Ascon tecnologic KM2 Engineering Manual Download Page 10](http://html1.mh-extra.com/html/ascon-tecnologic/km2/km2_engineering-manual_2981538010.webp)
Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 10
[24] o3Ac - Out 3 action
Available:
When [9] io3.F = out3 and [22] o3F is different
from
nonE
.
Range: dir
Direct action;
rEU
Reverse action;
dir.r
Direct action with reverse LED indication;
rEU.r
Reverse action with reverse LED indication.
For more details see [18] o1.Ac parameter.
]
AL1 Group - Alarm 1 parameters
[25] AL1t - Alarm 1 type
Available:
Always.
Range: •
When one or more outputs are programmed as
control output:
nonE
Alarm not used;
LoAb
Absolute low alarm;
HiAb
Absolute high alarm;
LHAo
Absolute band alarm with alarm indication
out of the band;
LHAi
Absolute band alarm with alarm indication
inside the band;
SE.br
Sensor break;
LodE
Deviation low alarm (relative);
HidE
Deviation high alarm (relative);
LHdo
Relative band alarm with alarm indication
out of the band;
LHdi
Relative band alarm with alarm indication
inside the band;
•
When no output is programmed as control output;
nonE
Alarm not used;
LoAb
Absolute low alarm;
HiAb
Absolute high alarm;
LHAo
Absolute band alarm with alarm indication
out of the band;
LHAi
Absolute band alarm with alarm indication
inside the band;
SE.br
Sensor break.
Notes: 1.
The relative and deviation alarms are “relative” to
the operative Set Point value.
LoAb
OUT
AL1
AL1
PV
HAL1
time
HiAb
off
off
off
OUT
AL1
AL1
PV
HAL1
time
off
off
off
ON
ON
ON
ON
LHAb
PV
AL1H
HAL1
time
off
off
off
LHde
OUT
AL1
AL1L
HAL1
PV
AL1H
SP
HAL1
time
OUT
AL1
-AL1L
HAL1
off
off
off
ON
ON
ON
ON
2.
The (SE.br) sensor break alarm will be ON when
the display shows
----
indication.
[26] Ab1 - Alarm 1 function
Available:
When [25] AL1t is different from
nonE
.
Range:
0... 15 with the following rule:
+1
Not active at Power ON;
+2
Latched alarm (manual reset);
+4
Acknowledgeable alarm;
+8
Relative alarm not active at Set Point change.
Example:
Setting Ab1 equal to 5 (1 + 4) the alarm 1 will be
“Not active at Power ON” and “Acknowledgeable”.
Notes: 1.
The “Not active at Power ON” selection allows to
inhibit the alarm function at instrument Power ON
or when the instrument detects a transfer from:
•
Manual mode (oPLo) to auto mode;
•
Stand-by mode to auto mode.
The alarm will be automatically enabled when the
measured value reaches, for the first time, the
alarm threshold ±hysteresis (in other words, when
the initial alarm condition disappears).
PWR ON
AL1
PV
time
off
off
Ab1 = +1
Ab1 = +0
off
off
ON
ON
ON
2.
A “Latched alarm” (manual reset) is an alarm
that will remain active even if the conditions that
generated the alarm no longer persist. Alarm
reset can be done only by an external command
(
button, digital inputs or serial link).
Alarm reset
Alarm reset
AL1
PV
time
off
off
Ab1 = +2
Ab1 = +0
off
off
ON
ON
3.
An “Acknowledgeable” alarm is an alarm that can
be reset even if the conditions that generated the
alarm are still present. Alarm acknowledge can be
done only by an external command (
button,
digital inputs or serial link).
Alarm ACK
Alarm ACK
AL1
PV
time
off
off
Ab1 = +4
Ab1 = +0
off
off
off
ON
ON
ON
4.
A “relative alarm not active at Set Point change”
is an alarm that masks the alarm condition after
a Set Point change until process variable reaches
the alarm threshold ± hysteresis.
Sp2
Sp1
PV
time
Ab1 = +8
Ab1 = +0
ON
off
off
AL1
off
off
off
AL1
ON
ON
ON
ON
5.
The instrument does not store in EEPROM the
alarm status. For this reason, the alarm status
will be lost if a power down occurs.