Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 9
2.
The power failure indicator is reset when the
instrument detects an alarm reset command from
key, digital input or serial link.
3.
When no control output is programmed, all the
relative alarm (when present) are forced to
nonE
(not used).
[15] A.o1L - Initial scale value of the analogue
retransmission
Available:
When Out 1 is a linear output and [14] O1F is
equal to r.IMP, r.Err, r.SP, r.SEr or r.Po.
Range: -1999
to
[16] Ao1H.
[16] A.o1H - Full scale value of the analogue
retransmission
Available:
When Out 1 is a linear output and [14] O1F is
equal to r.IMP, r.Err, r.SP, r.SEr or r.Po.
Range: [15] Ao1L
to
9999
.
[17] o1.AL - Alarms linked to Out 1
Available:
When [14] o1F = AL.
Range:
0... 63 with the following rules:
+1
Alarm 1;
+2
Alarm 2;
+4
Alarm 3;
+8
Heater break down alarm;
+16
Sensor break (burn out);
+32
Overload on Out3 (short circuit on the Out3).
Example 1:
Setting 3 (2+1) the output will be driven by the
alarm 1 and 2 (OR condition).
Example 2:
Setting 13 (8+4+1) the output will be driven by
alarm 1 + alarm 3 + loop break alarm.
[18] o1.Ac - Out 1 action
Available:
When [14] o1F is different from
nonE
.
Range: dir
Direct action;
rEU
Reverse action;
dir.r
Direct action with reverse LED indication;
rEU.r
Reverse action with reverse LED indication.
Notes: 1.
Direct action: the output repeats the status of the
driven element. Example: the output is an alarm
output with direct action. When the alarm is ON,
the relay will be energized (logic output 1).
2.
Reverse action: the output status is the opposite of
the status of the driven element. Example: the output
is an alarm output with reverse action. When the
alarm is OFF, the relay will be energized (logic output
1). This setting is usually named “fail-safe” and it
is generally used in dangerous process in order
to generate an alarm when the instrument power
supply goes OFF or the internal watchdog starts.
[19] o2F - Out 2 function
Available:
When the instrument has out 2 option.
Range: nonE
Output not used. With this setting the
status of this output can be driven directly
from serial link;
H.rEG
Heating output;
c.rEG
Cooling output;
AL
Alarm output;
t.out
Timer output;
t.HoF
Timer out - OFF in Hold;
P.End
Program end indicator;
P.HLd
Program hold indicator;
P.uit
Program wait indicator;
P.run
Program run indicator;
P.Et1
Program Event 1;
P.Et2
Program Event 2;
or.bo
Out-of-range or burn out indicator;
P.FAL
Power failure indicator;
bo.PF
Out-of-range, Burnout and Power failure
indicator;
St.By
Stand By status indicator;
diF1
Repeats the digital input 1 status;
diF2
Repeats the digital input 2 status;
on
Out 2 always ON;
riSP
Inspection request.
For other details see [14] O1F parameter.
[20] o2.AL - Alarms linked to Out 2
Available:
When [18] o2F = AL.
Range:
0... 63 with the following rule:
+1
Alarm 1;
+2
Alarm 2;
+4
Alarm 3;
+8
Heater break down alarm;
+16
Sensor break (burn out);
+32
Overload on Out3 (short circuit on the Out3).
For more details see [17] o1.AL parameter.
[21] o2Ac - Out 2 action
Available:
When [19] o2F is different from
nonE
.
Range: dir
Direct action;
rEU
Reverse action;
dir.r
Direct action with reverse LED indication;
rEU.r
Reverse action with reverse LED indication.
For more details see [18] o1.Ac parameter.
[22] o3F - Out 3 function
Available:
When the instrument has out 3 option.
Range: nonE
Output not used. With this setting the
status of this output can be driven directly
from serial link;
H.rEG
Heating output;
c.rEG
Cooling output;
AL
Alarm output;
t.out
Timer output;
t.HoF
Timer out - OFF in Hold;
P.End
Program end indicator;
P.HLd
Program hold indicator;
P.uit
Program wait indicator;
P.run
Program run indicator;
P.Et1
Program Event 1;
P.Et2
Program Event 2;
or.bo
Out-of-range or burn out indicator;
P.FAL
Power failure indicator;
bo.PF
Out-of-range, Burnout and Power failure
indicator;
St.By
Stand By status indicator.
For other details see [14] O1F parameter.
[23] o3.AL - Alarms linked to Out 3
Available:
When [9] Io3.F = Out 3 and [22] o3F = AL.
Range:
0... 63 with the following rule:
+1
Alarm 1;
+2
Alarm 2;
+4
Alarm 3;
+8
Heater break down alarm;
+16
Sensor break (burn out);
+32
Overload on Out 3 (short circuit on the Out 3).
For more details see [17] o1.AL parameter.