Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 18
(maximum rate of rise for negative Set Point change).
[93] Pr.Et - Time of the End program indication
Available:
When [91] Pr.F is different from
nonE
.
Range: oFF
Function not used;
00.01... 99.59
minutes and seconds;
inF
Forced to ON.
Note:
Setting [93] Pr.Et = inF the end program indication will
go OFF only when a reset command or a new RUN
command is detected.
[95] Pr.S1 - Set Point of the first soak
Available:
When [91] Pr.F is different from
nonE
or [91] Pr.F
is different from
S.uP.d
.
Range:
From
[75] SPLL
to
[76] SPHL
.
[96] Pr.G1 - Gradient of the first ramp
Available:
When [91] Pr.F is different from
nonE
or [91] Pr.F
is different from
S.uP.d
.
Range: 0.1... 999.9
engineering units per minute;
inF
Step transfer.
[97] Pr.t1 - Time of the first soak
Available:
When [91] Pr.F is different from
nonE
.
Range: 0.00... 99.59
Time units.
[98] Pr.b1 - Wait band of the first soak
Available:
When [91] Pr.F is different from
nonE
or [91] Pr.F
is different from
S.uP.d
.
Range: OFF... 9999
engineering units.
Note:
The wait band suspends the time counting when
the measured value goes out of the defined band
(guaranteed soak).
Temperature
Wait
Wait
Soak x
Soak x
Ramp x + 1
Ramp x
Wait
Soak SP
Wait
SP
Measure
[99] Pr.E1 - Events of the first group
Available:
When [91] Pr.F is different from
nonE
or [91] Pr.F
is different from
S.UP.d
.
Range: 00.00... 11.11
where:
0
Event OFF;
1
Event ON.
Event 1 status during ramp
Event 2 status during ramp
Event 1 status during soak
Event 2 status during soak
Display
Ramp
Soak
Event 1
Event 2
Event 1
Event 2
00.00
off
off
off
off
10.00
on
off
off
off
01.00
off
on
off
off
11.00
on
on
off
off
00.10
off
off
on
off
10.10
on
off
on
off
01.10
off
on
on
off
11.10
on
on
on
off
Display
Ramp
Soak
Event 1
Event 2
Event 1
Event 2
00.01
off
off
off
on
10.01
on
off
off
on
01.01
off
on
off
on
11.01
on
on
off
on
00.11
off
off
on
on
10.11
on
off
on
on
01.11
off
on
on
on
11.11
on
on
on
on
[100] Pr.S2 - Set Point of the second soak
Available:
When [91] Pr.F is different from
nonE
.
Range:
From
[75] SPLL
to
[76] SPHL
;
oFF
Program end.
Note:
It is not necessary to configure all steps.
When you use for example 2 groups only, it is
sufficient to set the Set Point of the third group equal
to OFF. The instrument will mask all the following
parameters of the programmer.
[101] Pr.G2 - Gradient of the second ramp
Available:
When [91] Pr.F is different from
nonE
and
[100] Pr.S2 is different from
oFF
.
Range: 0.1... 999.9
engineering units per minute;
inF
Step transfer.
[102] Pr.t2 - Time of the second soak
Available:
When [91] Pr.F is different from
nonE
and
[100] Pr.S2 is different from
oFF
.
Range: 0.00... 99.59
time units.
[103] Pr.b2 - Wait band of the second soak
Available:
When [91] Pr.F is different from
nonE
and
[100] Pr.S2 is different from
oFF
.
Range: OFF... 9999
engineering units.
Note:
For more details see [98] Pr.b1 parameter.
[104] Pr.E2 - Events of the second group
Available:
When [91] Pr.F is different from
nonE
and
[100] Pr.S2 is different from
oFF
.
Range:
00.00... 11.11 where:
0
Event OFF;
1
Event ON.
Note:
For more details see [99]Pr.E1 parameter.
[105] Pr.S3 - Set Point of the third soak
Available:
When [91] Pr.F is different from
nonE
and
[100] Pr.S2 is different from
oFF
.
Range:
From
[75] SPLL
to
[76] SPHL
;
oFF
Program end.
Note:
For more details see [100] Pr.S2 parameter.
[106] Pr.G3 - Gradient of the third ramp
Available:
When [91] Pr.F is different from
nonE
,
[102] Pr.S2 is different from
oFF
and
[105] Pr.S3 is different from
oFF
.
Range: 0.1... 999.9
engineering units per minute;
inF
Step transfer.
[107] Pr.t3 - Time of the third soak
Available:
When [91] Pr.F is different from
nonE
,
[100] Pr.S2 is different from
oFF
and
[105] Pr.S3 is different from
oFF
.
Range:
0.00... 99.59 time units.