Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 21
[121] di.CL - Display colour
Available:
Always.
Range: 0
The display colour is used to show the actual
deviation (PV - SP);
1
Display red (fix);
2
Display green (fix);
3
Display orange (fix).
[122] AdE - Deviation for display colour management
Available:
When [121] di.CL = 0.
Range: 1... 9999
engineering units.
[123] diS.t - Display time out
Available:
Always.
Range:
oFF
The display is always ON;
0.1... 99.59
minutes and seconds.
Note:
This function allows to turn OFF the display when
no alarm is present and no action is made on the
instrument. When diS.t is different from
oFF
and no
button is pressed for more than the programmed time
out, the display goes OFF and only 4 segments of
the less significant digit are turned ON in sequence in
order to show that the instrument is working correctly.
If an alarm occurs or a button is pressed, the display
will come back to the normal operation.
[124] FiLd - Filter on the displayed value
Available:
Always.
Range:
oFF
Filter disabled;
0.1... 20.0
engineering units.
Note:
This is a “window filter” related to the Set Point, it is ap-
plied to the displayed value only and has no effect on the
other functions of the instrument (control, alarms, etc.).
[125] Reserved
[126] dSPu - Status of the instrument at Power ON
Available:
Always.
Range: AS.Pr
Starts in the same way it was prior to the
power down;
Auto
Starts in Auto mode;
oP.0
Starts in manual mode with a power output
equal to zero;
St.bY
Starts in stand-by mode.
Notes: 1.
When you change the value of [127] oPr.E, the in-
strument forces [128] oPEr parameter equal to Auto.
2.
During program execution the instrument stores
the segment currently in use and, by a 30 minutes
interval, it stores also the elapsed time of the soaks.
If a power down occurs during program execu-
tion, at the next power ON the instrument is able
to continue the program execution starting from
the segment in progress at power down and, if the
segment was a soak, it is also capable to restart
from the soak time minus the stored elapsed time.
In order to obtain this features, the “[126] dSPu -
Status of the instrument at Power ON” parameter
must be set to “AS.Pr”.
If the “[126] dSPu” parameter is different from
“AS.Pr” The memorization function is inhibited.
3.
Setting [126] dSPu equal to AS.Pr, if the power
down occurs when the instrument is in MANUAL
mode, at Power ON the instrument will re-start in
manual mode with the same power used prior to
the power down.
[127] oPr.E - Operative modes enabling
Available:
Always.
Range: ALL
All modes can be selected through the next
parameter.
Au.oP
Only Auto and Manual (oPLo) modes can
be selected by the next parameter;
Au.Sb
Only Auto and Stand-by modes can be
selected by the next parameter.
Note:
Manual changing the value of [127] oPr.E, the
instrument forces parameter [138] oPEr = Auto.
[128] oPEr - Operative mode selection
Available:
Always.
Range: •
When [127] oPr.E = ALL:
Auto
Auto mode;
oPLo
Manual mode;
St.bY
Stand by mode.
•
When [127] oPr.E = Au.oP:
Auto
Auto mode;
oPLo
Manual mode.
•
When [127] oPr.E = Au.Sb:
Auto
Auto mode;
St.bY
Stand by mode.
]
Ser group - Serial link parameter
[129] Add - Instrument address
Available:
Always.
Range: oFF
Serial interface not used;
1... 254
.
[130] bAud - Baud rate
Available:
When [129] Add different from
oFF
.
Range: 1200
1200 baud;
2400
2400 baud;
9600
9600 baud;
19.2
19200 baud;
38.4
38400 baud.
[131] trSP - Selection of the value to be
retransmitted
(Master)
Available:
When [129] Add different from
oFF
.
Range: nonE
Retransmission not used (the instrument is a
slave);
rSP
The instrument become a Master and it re-
transmits the operative Set Point;
PErc
The instrument become a Master and it re-
transmits the power output.
Note:
For more details see [82] SP.rt (Remote Set Point
type) parameter.
]
COn Group - Consumption parameters
[132] Co.tY - Count type
Available:
Always.
Range: oFF
Not used;
1
Instantaneous power (kW);
2
Consumed energy (kWh);
3
Energy used during program execution. This
measure starts from zero when a program runs
end stops at the end of the program. A new
program execution will reset the value.
4
Total worked days: Number of hours the instru-
ment is turned ON divided by 24.
5
Total worked hours: Number of hours that the