Ascon tecnologic KM2 Engineering Manual Download Page 22

Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 22

instrument is turned ON.

6

  Total worked days with threshold: Number of 

hours the instrument is turned ON divided by 24, 
the controller is forced in stand-by when Co.ty 
value reaches the threshold set in [135] h.Job.

7

  Total worked hours with threshold: number of 

hours that the instrument is turned ON, the 
controller is forced in stand-by when Co.ty value 
reaches the threshold set in [135] h.Job.

8

  Totalizer of control relay worked days: Number 

of hours the control relay has been in ON condi-
tion, divided by 24.

9

  Totalizer of control relay worked hours: Number of 

hours the control relay has been in ON condition.

10

  Totalizer of control relay worked days with 

threshold: Number of hours the control relay 
has been in ON condition divided by 24, the 
controller is forced in stand-by when Co.ty value 
reaches the threshold set in [135] h.Job.

11

  Totalizer of control relay worked hours with 

threshold: Number of hours the control relay 
has been in ON condition, the controller is 
forced in stand-by when Co.ty value reaches 
the threshold set in [135] h.Job.

Notes:   1. 

When the control action is made using the linear 
output or the servomotor, the valid counting 
methods are 4, 5, 6, 7.

2. 

Selections 4... 11 represent an internal count: 
these modes calculate the instrument work in 
hours or days.  When the count reaches the 
threshold set with parameter [135] h.Job the 
display shows “r.iSP” (Inspection Requested).
The count reset (with r.iSP cancellation) can be 
done only by changing  the threshold value - pa-
rameter [135] h.Job.  Using counting methods 6, 7, 
10, 11, the count reset causes the controller to exit 
the stand-by status returning to the control status.

[133] UoLt - Nominal Voltage of the load

Available: 

When [132] Co.tY = ist or [132] Co.tY = h or  
[132] Co.tY = S.S.

Range: 1... 9999

 (V).

[134] cur - Nominal current of the load

Available: 

When [132] Co.tY = ist or [132] Co.tY = h or 
[132] Co.tY = S.S.

Range: 1... 999

 (A).

[135] h.Job - Threshold of the working period

Available: 

When [132] Co.tY = tot.d or [132] Co.tY = tot.H.

Range: 

oFF = Threshold not used;
1... 9999 days when [132] Co.tY = 4;
1... 9999 hours when [132] Co.tY = 5.

[136] t.Job - Worked time

 (not resettable)

Available: 

Always.

Range: 

1... 9999 days.

]

CAL group - User calibration group

This function allows to calibrate the complete measuring 
chain and to compensate the errors due to:

 

Sensor location;

 

Sensor class (sensor errors);

 

Instrument accuracy.

[137] AL.P - Adjust Low Point

Available: 

Always.

Range: 

From 

-1999

 to 

(AH.P - 10)

 engineering units.

Note: 

The minimum difference between AL.P and AH.P is 
equal to 10 Engineering Units.

[138] AL.o - Adjust Low Offset

Available: 

Always.

Range: -300... +300

 engineering units.

[139] AH.P - Adjust High Point

Available: 

Always.

Range: 

From 

(AL.P + 10)

 to 

9999

 engineering units.

Note: 

The minimum difference between AL.P and AH.P is 
equal to 10 Engineering Units.

[140] AH.o - Adjust High Offset 

Available: 

Always.

Range: -300... +300

 Engineering Units.

Example:

 Environmental chamber with an operative range: 

10... 100°C.

1. 

Insert in the chamber a reference sensor connected with 
a reference instrument (usually a calibrator).

2. 

Power ON the instrument and insert a Set Point equal to 
the min. value of the operative range (e.g.: 10°C).  When 
the temperature in the chamber is steady, take note of the 
temperature measured by the reference system (e.g.: 9°C).

3. 

Set [137] AL.P = 10 (low working point) and [138] ALo = -1  
(the difference between the reading of the instrument 
and the one of the reference system).  Note that after this 
set the measured value of the instrument is equal to the 
measured value of the reference system.

4. 

Set a Set Point equal to the maximum value of the 
operative range (e.g. 100°C).  When the temperature 
in the chamber is steady, take note of the temperature 
measured by the reference system (e.g. 98°C).

5. 

Set [139] AH.P = 100 (low working point) and [140] AHo = +2  
(the difference between the reading of the instrument 
and the one of the reference system).  Note that after this 
set the measured value of the instrument is equal to the 
measured value of the reference system.

AH.P = 100°C

AH.o = 2

AL.o = -1

AH.P = 10°C

Real curve

Modified curve

5.7  Exiting the configuration level

The most important configuration step is completed.
In order to exit from configuration parameter procedure, 
proceed as follows:

• 

Push 

 button.

• 

Push 

 button for more than 10 s.   

The instrument returns to the “Standard display”.

Summary of Contents for KM2

Page 1: ...protection IP65 is desired the optional gasket must be mounted 1 2 Dimensions 1 2 1 Controller with non removable terminals 63 3 14 11 44 5 PV AT 48 48 1 2 2 Removable terminals 40 15 5 18 85 26 15 8...

Page 2: ...ration According to EN 60751 A2 2 3 5 V and mV Input mV V _ _ 1 2 Input impedance 1 M for mV Input 500 k for Volt Input 2 3 6 mA Input 0 4 20 mA input wiring for passive transmitter using the auxiliar...

Page 3: ...Logic level 1 12 V 20 15 mA max Current Analogue Output mA 7 8 mA output 0 4 20 mA galvanically isolated RL max 600 Voltage Analogue Output V 7 8 V output 0 2 10 V galvanically isolated RL min 500 2...

Page 4: ...m 1 78 0 023 x 1 78 0 023 in Weight 180 g max Power supply 24 240 VAC DC 10 Power consumption 5 VA max Insulation voltage 3000 V rms according to EN 61010 1 Display updating time 500 ms Sampling time...

Page 5: ...he instrument has a complete parameter set that allows the user to adapt the controller to the destination application Note The instrument normally shows only the parameters consistent with the specif...

Page 6: ...20 0 20 mA linear 4 20 4 20 mA linear 0 5 0 5 V linear 1 5 1 5 V linear 0 10 0 10 V linear 2 10 2 10 V linear When the code of the input type is equal to e see How to order paragraph J TC J 50 1000 C...

Page 7: ...g 9 io3F from on to Out3 makes the 22 O3F parameter visible and equal to nonE 10 diF1 Digital input 1 function Available Always Range oFF No function 1 Alarm Reset status 2 Alarm acknowledge ACK statu...

Page 8: ...ollowing table Digital Input 1 Digital Input 2 Operative Set Point Off Off Set Point 1 On Off Set Point 2 Off On Set Point 3 On On Set Point 4 4 When 10 diF1 is equal to 21 11 diF2 is forced to 21 up...

Page 9: ...Output not used With this setting the status of this output can be driven directly from serial link H rEG Heating output c rEG Cooling output AL Alarm output t out Timer output t HoF Timer out OFF in...

Page 10: ...ion Available When 25 AL1t is different from nonE Range 0 15 with the following rule 1 Not active at Power ON 2 Latched alarm manual reset 4 Acknowledgeable alarm 8 Relative alarm not active at Set Po...

Page 11: ...ysteresis equal to 25 C 31 AL1d Alarm 1 delay Available When 25 AL1t is different from nonE Range 0 oFF 1 9999 seconds Note The alarm goes ON only when the alarm condition persists for a time longer t...

Page 12: ...larm with alarm indication out of the band LHAi Absolute band alarm with alarm indication inside the band SE br Sensor break Note The relative alarm are relative to the current Set Point this may be d...

Page 13: ...ilable When 49 Ct So is different from oFF Range 0 Automatic reset 1 Manual reset 2 Acknowledgeable 54 Ct Ld Load current threshold Available When 49 Ct So is different from oFF Range 0 Disabled 1 999...

Page 14: ...and 1 00 it is possible to slow down the instrument action during Set Point approach Setting Fuoc 1 this function is disabled PV SP time 2 1 3 Available When 57 cont PID Range 0 2 00 Note Fast auto tu...

Page 15: ...tH parameter 2 When the power limiter has a negative value the limit is applied to the cooling action the soft start function will be aborted when the measured value is lower or equal to SS tH paramet...

Page 16: ...controllers The Slave zones use it as a Set Point trim The first zone is the master zone and it uses a Set Point equal to 210 C The second zone has a local Set Point equal to 45 C The third zone has...

Page 17: ...m steps Some additional parameters allow to define the time scale the automatic RUN conditions and the instrument behaviour at the end of the program Notes 1 All steps can be modified during program e...

Page 18: ...ent 1 Event 2 Event 1 Event 2 00 01 off off off on 10 01 on off off on 01 01 off on off on 11 01 on on off on 00 11 off off on on 10 11 on off on on 01 11 off on on on 11 11 on on on on 100 Pr S2 Set...

Page 19: ...m Hold rES Program reset Note This parameter allows to manage program execution by a parameter PAn group Operator HMI 116 PAS2 Level 2 password Limited access level Available Always Range oFF Level 2...

Page 20: ...o when ON OFF control is selected ct on CT measure during ON ct OF CT measure during OFF ct iS Instantaneous CT measurement 120 L dSP Secondary Display Management Available Always Range nonE Display O...

Page 21: ...estart from the soak time minus the stored elapsed time In order to obtain this features the 126 dSPu Status of the instrument at Power ON parameter must be set to AS Pr If the 126 dSPu parameter is d...

Page 22: ...ays when 132 Co tY 4 1 9999 hours when 132 Co tY 5 136 t Job Worked time not resettable Available Always Range 1 9999 days CAL group User calibration group This function allows to calibrate the comple...

Page 23: ...9 td Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds 2 The upper display will show PASS while the lower display will show 0 3 By and buttons set a password equal to 8...

Page 24: ...If no button is pressed for more than 10 seconds the instrument goes back to the standard display and the new value of the last selected parameter will be lost 7 2 Enter the Limited access level The i...

Page 25: ...sing the and buttons assign to this parameter the desired value 3 Push no buttons for more than 5 second or push the button In both cases the instrument stores the new value and returns to the Standar...

Page 26: ...program is running the door is locked Application Example 2 edge bending machine with glue tank for wood At the working temperature the hot melt rapidly oxidizes and runs down from the dispenser For t...

Page 27: ...and by mode parameter setting 2 If you set stand by mode during program execution the program will be aborted 3 If you set stand by mode during self tune execution the self tune function will be abort...

Page 28: ...t there are no loose terminals 5 Before turning ON the instrument make sure it is perfectly dry 6 Apply the power supply to the instrument 9 3 Disposal The appliance or the product must be disposed of...

Page 29: ...52 F Ir J Exergen IRS J 46 785 C 50 1445 F Ir cA Exergen IRS K 46 785 C 50 1445 F Ptc PTC KTY81 121 55 150 C 67 302 F ntc NTC 103 AT2 50 110 C 58 230 F 0 60 0 60 mV 12 60 12 60 mV 0 20 0 20 mA 4 20 4...

Page 30: ...output 0 NonE Output not used H rEG Heating output c rEG Cooling output r inP Measure retransmission r Err Error SP PV retransmission r SP Set Point retransmission r SEr Serial value retransmission r...

Page 31: ...3 1 Alarm 1 2 Alarm 2 4 Alarm 3 8 Heater Break Down 16 Sensor Break 32 Overload on output 3 AL1 21 o2Ac Out 2 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse...

Page 32: ...n stand by mode 2 Alarm 1 enabled in out of range conditions 3 Alarm 1 enabled in stand by mode and out of range conditions 0 AL2 group Alarm 2 parameters no Param Description Dec Point Values Default...

Page 33: ...ditions 1 Alarm 1 enabled in stand by mode 2 Alarm 1 enabled in out of range conditions 3 Alarm 1 enabled in stand by mode and out of range conditions 0 HBD group Heater Break Down Parameters no Param...

Page 34: ...01 99 99 1 00 68 tcc Cooling output cycle time C rEG 1 0 2 130 0 s 20 0 69 rS Manual reset Integral pre load 1 100 0 100 0 0 0 70 od Delay at Power ON 2 0 00 oFF 00 01 99 59 hh mm oFF 71 St P Maximum...

Page 35: ...s and seconds inF Forced to ON oFF 95 Pr S1 Set Point of the first soak dP From SPLL to SPHL 0 96 Pr G1 Gradient of the first ramp 1 0 1 999 9 Engineering Unit minute inF Step transfer inF 97 Pr t1 Ti...

Page 36: ...r is running the display shows the timer counting up ti du When the timer is running the display shows the timer counting down PErc Percent of the power output used during soft start ct on Current mea...

Page 37: ...measure starts from zero when a program runs end stops at the end of the program A new program execution will reset the value 4 Total worked days number of hours the instrument is turned ON divided by...

Page 38: ...eters no Param Description Dec Point Values Default 137 AL P Adjust Low Point dp From 1999 to AH P 10 in engineering units 0 138 AL o Adjust Low Offset dp 300 300 E U 0 139 AH P Adjust High Point dp F...

Page 39: ...Ascon Tecnologic KM2 Line ENGINEERING MANUAL PAG 39...

Page 40: ...Ascon Tecnologic KM2 Line ENGINEERING MANUAL PAG 40...

Reviews: