Installation and Operation Manual
UPAC- Unite Packet for Messaging and Alarm
34
5.1.2
Ascom Line Protocol
1
The following settings can be selected/changed:
2
Click “Activate”.
Settings
Description
Enabled:
Yes/No selection. Default: No
Name:
Description of the channel
Serial port:
Port selection (1,2,3)
Default: None
Port 3 will be selected when set from the Wizard,
but all three ports can be configured here. Note
that only one at the time can be used.
Bit rate:
Select bit rate.
Default: 9600 bits/s
Mode:
Select mode.
Default: 8 Data bits, Even parity
Flow control:
Used for handshaking control. Default: None
Default Call ID:
Number to call if not specified in the external
equipment. Default: 000
Default display message:
Message to display if not specified in the external
equipment. Default: BLANK
Default message priority:
Priority if not specified in the external equipment.
Default: 7 (Normal)
Default beep code:
Beep code if not specified in the external
equipment.
Default: 2 beeps
Transmission delay (x10 ms):
How long to wait before transmission to external
equipment. Default: 30 milliseconds
Status to ext equipment:
If status characters ACK/NAK shall be sent on
protocol level to external equipment.
Default: Yes
Start character :
Start character for the message.
Default: < (3C Hex)
End character:
End character for the message.
Default: > (3E Hex)
Record separator character:
Record separator character for the message.
Default: / (2F Hex)
ACK character:
Character for positive acknowledge of the message
on protocol level
. Default: A (41 Hex)
NAK character:
Character for negative acknowledge of the
message
on protocol level
. Default: N (4E Hex)
ASCII conversion table:
Makes it possible to convert display message
characters.