TD 92483GB
2008-06-05/ Ver. B
Installation and Operation Manual
UPAC- Unite Packet for Messaging and Alarm
8
2.7
Accessing the UPAC
2.7.1
Getting Started
When accessing UPAC the first time, follow the instructions in the
(enclosed in delivery), or see
on page 95 which holds a
copy of the printed leaflet.
Note:
The IP address must not change during operation because renew of IP address via
DHCP is not handled. Other equipment connected to this product also expects a fixed IP
address in some cases. If the IP plan is changed, this product must be restarted to update
the IP address. Otherwise there is a risk for IP address collision.
Note:
Attach the ferrite bead on the power supply cable. Follow the enclosed assembly
card for EMC protection, M0271500.
2.7.2
Connect Cables
A cable to the DECT Exchange can be ordered separately, refer to the
Unite Packet for Messaging and Alarm
. If you want to make your own cable,
refer to the descriptions in
For connections to digital inputs/outputs and the error relay, refer to
and
1
Break off suitable sections before inserting cables, refer to
2
Connect the DECT Exchange or GSM modem to connector J11 (RS232:1).
3
Connect external equipment to connector J7 (RS232:3).
4
For remote management use connector J8 (RS232:2).
Figure 5. Cable connections
Figure 9.
J13
J12
J11
J
8
J7
J24
J14
J6
J5
J20
RS232:3
ETH
900
900
RS232:2
S4
S5
S1
S2
2
2
1
1
4
1
4
1
DE
C
T Ex
c
h
a
nge or GSM modem
LAN or P
C
+12V GND
Error rel
a
y
output
00
8
1 Extern
a
l +12 V
2 IN1
3 IN2
4 OUT1
5 OUT2
6 Extern
a
l GND
J16
AUX Inputs/ Outputs
Extern
a
l e
q
uipment
(ESPA 4.4.4 / Line proto
c
ol)
RS232:1
Remote
m
a
n
a
gement