10.2.3 Summary Fault Actions
In the
Summary Fault Actions
page, it is possible to set actions to start when the first
persistent fault occurs and/or when there are no remaining persistent faults. The actions
that can be set are:
• Activating error relay and outputs set up on the
I/O Setup
page for the defined time or
as long as there are persistent faults.
• Sending messages when the first fault occurs and when no faults remain.
• Sending SNMP traps when the first fault occurs and when no faults remain.
• Sending E-mail when the first fault occurs and when no faults remain.
1
Click “Configuration” on the start page.
2
Select Fault Handling > Summary Fault Actions in the left menu on
UPAC
Configuration
page.
Activating Error Relay/Outputs
• Error Relay
1
To activate the error relay, select the check box for
Indicates Fault
.
The error relay will be released when activated.
2
Set the duration in seconds. If duration is not set, the error relay will be released
until no persistent faults remain.
3
Click “Save” at the bottom of the page.
The error relay can manually be reset from the
Active Faults
page.
• Outputs
1
Select an output and click “Add”.
2
Set the duration in seconds. If the duration is not set, the output is active until no
persistent faults remain.
3
Click “Save” at the bottom of the page.
The outputs can manually be reset from the
I/O Setup
Figure 67.