TD 92483GB
2008-06-05/ Ver. B
Installation and Operation Manual
UPAC- Unite Packet for Messaging and Alarm
92
Example 2
When the door to one of the cold-storage rooms is opened, the input from Cold-storage
room is activated. If the door is open longer than 2 minutes a message is sent and the
lamp above the door is lit. If the door still is open after 10 minutes another message is
sent. After 15 minutes another message is sent and the siren starts to sound. When the
door is closed the siren and lamp are turned off.
Three alarm actions are created. One that handles the alarm called “Cold-storage room
open”, one called "Cold-storage room open very long" and one called "Cold-storage
room closed".
Cold-storage room 1, door open
Input Triggers: “Cold-storage door open” and “Cold-storage door still open”
When the door has been open for 2 minutes (120 seconds), the action is started. The
action shall not be repeated so the “Repetition time” is not stated, and the value in the
“Max. No. of Repetitions” field has no meaning.
When the door has been open for 10 minutes (600 seconds), another message is sent as a
reminder. A separate Alarm Action is required if a different beep-code is desired.
Actions Activate Output Action and Send Message Actions
Figure 54. Alarm Action, Cold-storage room open.
For Activate Output Action, the duration is here set to max value 3600.
Figure 121.