information in the sent Status Log and force the equipment to generate traps to get
detailed information.
Default SNMP Trap Action
The default action will be matched for all traps that are not matched by any other actions
that are set up. In the Status Log, the module will be set to “-” and the IP address and
Event Description will be copied from the received trap.
1
Click “Configuration” on the start page.
2
Select Supervision > SNMP Traps in the left menu on
UPAC Configuration
page.
Figure 22. The default settings for SNMP traps action.
Change Status Level
1
Click “Setup”.
Figure 23. The default SNMP trap is enabled to receive information.
2
Select which level the sent Status Log should have, or select “No Log” to not
generate a Status Log when a trap only matching the default action.
3
Enter an event description to be included in the Status Log.
4
Select the check box
Include trap data
, if received trap data should be included in
the log message.
5
Click “Save”.
Add/Change SNMP Trap Action
This is used when SNMP traps from specific modules or with certain messages should be
handled individually. The IP address in the received trap should match the defined pattern
Figure 60.
Figure 61.