Angle measurement inaccuracy
±0.2 degrees (15…300 V)
±1.5 degrees (1…15 V)
Voltage measurement bandwidth (freq.)
7…75 Hz fundamental, up to the 31
st
harmonic voltage
Terminal block connection
Terminal block
Phoenix Contact PC 5/8-STCL1-7.62
Solid or stranded wire
Maximum wire diameter
6 mm
2
Input impedance
24.5…24.6 M
Ω
Burder (50/60 Hz)
<0.02 VA
Thermal withstand
630 V
RMS
(continuous)
NO
NOTE!
TE!
Voltage measurement accuracy has been verified with 50/60 Hz.
The amplitude difference is 0.2 % and the angle difference is 0.5 degrees higher at 16.67 Hz and other
frequencies.
9.1.1.3 Power and energy measurement
Table. 9.1.1.3 - 155. Power and energy measurement accuracy
Power measurement P, Q, S
Frequency range 6…75 Hz
Inaccuracy
0.3 % <1.2 × I
N
or 3 VA secondary
1.0 % >1.2 × I
N
or 3 VA secondary
Energy measurement
Frequency range 6…75 Hz
Energy and power metering inaccuracy
0.5% down to 1A RMS (50/60Hz) as standard
0.2% down to 1A RMS (50/60Hz) option available (see the order code for details)
9.1.1.4 Frequency measurement
Table. 9.1.1.4 - 156. Frequency measurement accuracy.
Frequency measurement performance
Frequency measuring range
6…75 Hz fundamental, up to the 31
st
harmonic current or voltage
Inaccuracy
10 mHz
9.1.2 CPU & Power supply
9.1.2.1 Auxiliary voltage
Table. 9.1.2.1 - 157. Power supply model A
Rated values
Rated auxiliary voltage
85…265 V (AC/DC)
Power consumption
< 7 W
< 15 W
A
AQ
Q-S215
-S215
Instruction manual
Version: 2.04
272
Summary of Contents for AQ-S215
Page 1: ...AQ S215 Bay control IED Instruction manual...
Page 249: ...Figure 7 4 151 Example block scheme A AQ Q S215 S215 Instruction manual Version 2 04 248...
Page 269: ...Figure 8 13 172 Device installation A AQ Q S215 S215 Instruction manual Version 2 04 268...
Page 287: ...10 Ordering information A AQ Q S215 S215 Instruction manual Version 2 04 286...