Activation (to LD/DL/DD)
Activation (to Live Live)
<35 ms
<60 ms
Reset
<40 ms
Bypass modes
Voltage check mode (excluding LL)
LL+LD, LL+DL, LL+DD, LL+LD+DL, LL+LD+DD, LL+DL+DD, bypass
U live > limit
U dead < limit
0.10…100.00 %U
N
, setting step 0.01 %U
N
0.00…100.00 %U
N
, setting step 0.01 %U
N
No
Notte!
e!
• Voltage is scaled to the primary amplitude; therefore, the different sized PT secondaries are
possible.
• The minimum voltage for direction and frequency solving is 20.0 %U
N
.
• U< dead limit is not in use when set to 0 %U
N
.
• When SYN3 is used, SYN1 and SYN2 must have the same reference voltage.
• In 3LN mode the synchronization to the L-N and L-L voltages is possible. In 3LL/2LL modes
the synchronization is only supported to the L-L voltage.
9.2.2 Monitoring functions
9.2.2.1 Current transformer supervision
Table. 9.2.2.1 - 176. Technical data for the current transformer supervision function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Residual current channel I
01
(Coarse) (optional)
Residual current channel I
02
(Fine) (optional)
Current input magnitudes
RMS phase currents
RMS residual current (I
01
, I
02
) (optional)
Pick-up
Pick-up current settings:
- I
SET
high limit
- I
SET
low limit
- I
SUM
difference
- I
SET
ratio
- I2/I1 ratio
0.10…40.00 × I
N
, setting step 0.01 × I
N
0.10…40.00 × I
N
, setting step 0.01 × I
N
0.10…40.00 × I
N
, setting step 0.01 × I
N
0.01…100.00 %, setting step 0.01 %
0.01…100.00 %, setting step 0.01 %
Inaccuracy:
- Starting IL1, IL2, IL3
- Starting I2/I1
- Starting I01 (1 A)
- Starting I02 (0.2 A)
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
±1.0 %I2
SET
/ I1
SET
or ±100 mA (0.10…4.0 × I
N
)
±0.5 %I0
SET
or ±3 mA (0.005…10.0 × I
SET
)
±1.5 %I0
SET
or ±1.0 mA (0.005…25.0 × I
SET
)
Time delay for alarm
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy_
- Definite time (I
M
/I
SET
ratio > 1.05)
±2.0 % or ±80 ms
Instant operation time (alarm):
- I
M
/I
SET
ratio > 1.05
<80 ms (<50 ms in differential protection relays)
Reset
Reset ratio
97/103 % of the pick-up current setting
Instant reset time and start-up reset
<80 ms (<50 ms in differential protection relays)
A
AQ
Q-S215
-S215
Instruction manual
Version: 2.04
280
Summary of Contents for AQ-S215
Page 1: ...AQ S215 Bay control IED Instruction manual...
Page 249: ...Figure 7 4 151 Example block scheme A AQ Q S215 S215 Instruction manual Version 2 04 248...
Page 269: ...Figure 8 13 172 Device installation A AQ Q S215 S215 Instruction manual Version 2 04 268...
Page 287: ...10 Ordering information A AQ Q S215 S215 Instruction manual Version 2 04 286...