Setting up an RTD measurement, the user first needs to set the measurement module to scan the
wanted RTD elements. A multitude of Modbus-based modules are supported. Communication requires
bitrate, databits, parity, stopbits and Modbus I/O protocol to be set; this is done at
Communication
→
Connections. Once communication is set, the wanted channels are selected at Communication
→
Protocols
→
ModbusIO. Then the user selects the measurement module from the three (3) available
modules (A, B and C), as well as the poll address. Additionally, both the module type and the
polled channels need to be set. When using a thermocouple module, the thermo element type also
needs to be set for each of the measurement channels. Once these settings are done the RTDs are
ready for other functions.
A
AQ
Q-S215
-S215
Instruction manual
Version: 2.04
97