Usually, a radially built medium-voltage network in rural areas consists of a short cable connection from
the substation to the overhead line, followed by a relatively long overhead line that normally ends with
the consumer. The consumer (residence, farm, etc.) can connect to basically any point in the overhead
line with a 20 kV/0.4 kV distribution transformer. The overhead line can have many branches, and it is
not uncommon (especially in rural areas) that there are multiple forest areas the line runs through
between the consumer connections. In longer lines in sparsely populated areas it is possible to isolate
areas of the overhead line by dividing it up with disconnectors (at least in branches).
This type of application normally uses an auto-recloser with two shots (one high-speed and one
delayed) which are triggered by earth fault protection or overcurrent protection. Short-circuit protection
is used for interlocking the auto-recloser in case a clear short-circuit fault occurs in the line.
Figure. 5.4.4 - 89. Example of assigning request signals.
Figure. 5.4.4 - 90. Example of shot settings (two requests and two initialized shots).
In this example, earth fault (REQ2) uses its own operating time settings, whereas the time delay for
overcurrent (REQ1) comes from the auto-recloser's own settings. Both fault types can initialize both of
the shots with different settings. If the fault evolves from earth fault into a multi-phase fault, the auto-
recloser uses the AR1 settings for the reclosing. In this example, the dead time between the first and
the second shot in REQ1 differs from the dead time in REQ2 because the air needs more time to cool
and de-ionize after an overcurrent or a multi-phase fault than it does after an earth fault. If the high-set
overcurrent stage activates in any situation, the auto-reclosing sequence is stopped, the final trip is
issued and the feeder closing is locked by the auto-recloser. A manual reset of the auto-recloser's lock
is required before one can attempt to close the breaker. A manual reset can be applied from SCADA or
locally from the relay's HMI.
Based on the example above, the following six (6) sections present the principle signaling of the auto-
recloser function. These are the auto-recloser sequence variations that can occur with this setup:
A
AQ
Q-S215
-S215
Instruction manual
Version: 2.04
142
Summary of Contents for AQ-S215
Page 1: ...AQ S215 Bay control IED Instruction manual...
Page 249: ...Figure 7 4 151 Example block scheme A AQ Q S215 S215 Instruction manual Version 2 04 248...
Page 269: ...Figure 8 13 172 Device installation A AQ Q S215 S215 Instruction manual Version 2 04 268...
Page 287: ...10 Ordering information A AQ Q S215 S215 Instruction manual Version 2 04 286...