31
English
9.15 Operating
mode
Depending on the treatment and control unit installed, you can decide whether to connect closure
of the section valves to closure of the control valve or make them independent.
•
“M” operating mode:
The section valves are closed or opened by operating the main valve, provided that the switch
for the section valves is suitably positioned; i.e. if the section switches are in the OFF position
(lever down), the sections will not be controlled by operating the main valve.
If one or more switches of the section valves are in the ON position (lever up), closing or opening
the main valve will also close or open the section valves.
•
“P” operating mode:
The section valves are controlled independently.
The opening or closing of the main valve does not affect the opening or closing of the section
valves.
MODEL CODE
Standard working SET
467302A - 467304A
M
467303 - 467305 - 467307 - 46732xx
P
Tab. 25
For further information on the type of operation of the BRAVO 3XX computer, refer
to ADD_IN code D30023, available for download from www.aragnet.com
• (Menu 53.0) - BRAVO SERIES 32X ONLY
This parameter sets the computer’s operating mode:
•
Mode “M
”: corresponds to programming option "
".
•
Mode “P
”: corresponds to programming option "
".
To set mode “P” on systems with centrifugal pump, enable option "
" and refer
to l’ADD_IN code D30023, available for download from www.aragnet.com.
BRAVO 32X SERIES ONLY
• Access programming as described in
par. 9.9 - Access to advanced programming
1) Press in sequence to scroll through the
parameters in the Advanced Menu, and
select Menu 53.0
2) Press in sequence to set the mode
During data modification:
A) Press to confirm the new value
B) Press to exit without modifying the value