STO Function
GT3000
72
IMGT30017EN
10. make sure that the "STO" alarm procedure is activated automatically and that the operating sequence cannot be restored up until
the failure has been repaired; otherwise, check the reasons for non-identification of the failure and proceed accordingly. Restart the
verifications from § 1;
11. disable the “STO” request, restore the connection to terminal XM70-3 or XM70-4 and restore protection devices, if any;
6A.6.6
Configuration example
The configuration example reported below includes:
An interlocked guard without any locking device
STO configuration according to category 3 EN 954-1
Controlled stop according to category 1 of EN 60204-1
Control outputs of inputs STO and Dren, according to category 3 or 4 of EN 954-1
Use of a safety module to control the guards, for stop category 1 according to EN 60204-1 and safety category 3 according to EN 954-1
Conductors of feedback signals (with short-circuit protection)
In case of a feedback error, automatic activation of the "STO" alarm procedure: the operating sequence cannot be restored up until the
failure is repaired
Operating sequence:
1.
When the guard opens, the instantaneous output of the safety module which controls relay K1 (whose NO contact disables the RUN control)
is opened.
2.
The delayed output of the safety module remains excited for the preset time (longer than the stop time required for the motor)
3.
The motor slows-down in a controlled way, up until it stops.
4.
Once the motor has stopped, the delayed output of the safety module which controls relays K2 and K3 (whose NO contacts disable the
Dren and STO controls) is opened.
5.
Now the motor is in the "SAFE TORQUE OFF" state and cannot generate any torque. In order to stop a revolving motor with a load torque
applied to the axis, install a mechanical brake.
F0
F1
T0
T3
T1
R1
T2
L1 L2 L3
L1 L2 L3
+
3
-
-
+
3
R2
Q2
XM1-13
02
43
XM1-24
XM1-20
XM70-4
XM70-3
XM70-1
XM70-2
-XM70
SAFETY
TORQUE
OFF
-F
-K3
+24Vdc
N/-
-R02
FBK ENABLE
-KX
START
(*)
-F
-Q2
-K1
-K2
-T2
SCADA PLUS
(*) Opzione: START comandato via PROFIBUS
+ F401
NOTE
-i relè K2 e K3 con contatti a guida forzata secondo Norma EN50205
NOTA
-un relè o funzione equivalente per ogni azionamento
-K3
FDB STO
FDB Enable
-T2-R02
-T2-XM70
-K2
N/-
-S2
Reset
-K1
11.3
-H1
-K2
11.4
-K3
11.4
A2
PE
Y33
Y34
48
14
24
32
3TK2827
58
24Vdc
-F
Y10
A1
Y11 Y12
Y22
Y21
13
23
31
47
57
-F
-F
24Vdc
N/-
-a relais or equivalent function for every drive
Option: START control via PROFIBUS
STOP TYPE: CAT.1 CONTROLLED
SAFETY LEVEL EN954-1 CAT.3
DRIVE TYPE WITH SAFE TORQUE OFF
-relais K2 and K3 with forced track contacts according to
Standard EN50205
02
43
3
4
24Vdc
DI8 Drive Enable
DI1Start
Riparo interbloccato
ma privo di blocco
Safety-guard interlocked
but without lock
Summary of Contents for GT3000
Page 1: ...GT3000 Hardware Software Manual www answerdrives com ...
Page 2: ......
Page 4: ......
Page 8: ...Table Of Contents GT3000 iv IMGT30017EN ...
Page 12: ...General Safety Precautions viii IMGT30017EN ...
Page 25: ...GT3000 Technical Data IMGT30017EN 13 Frames IV V VIN SVGT045 166 IP20 ...
Page 26: ...Technical Data GT3000 14 IMGT30017EN Frames IV V VIN SVGT045 166 IP54 ...
Page 28: ...Technical Data GT3000 16 IMGT30017EN Frames VII VIII IP00 SVGT200 521K SVGT200 470F ...
Page 29: ...GT3000 Technical Data IMGT30017EN 17 F series Frames 2xVII 2xVIII Parallel IP00 SVGT520 940M ...
Page 30: ...Technical Data GT3000 18 IMGT30017EN K series Frames 2xVII 2xVIII Parallel IP00 SVGT580 960K ...
Page 36: ...Installation GT3000 24 IMGT30017EN 3A 2 1 4 Frames VII VIII Installatiion ...
Page 58: ...GT3000 Installation 46 IMGT30004EN ...
Page 107: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 95 ...
Page 110: ...Terminal Boards and Power Schematics GT3000 98 IMGT30017EN ...