62
IMGT30017EN
6A.4
External Control power supply
An external power supply is generally needed to keep the field bus fed when the drive is not powered, and to monitor the drive in safety. The function is
available with:
a)
GT3000 arranged for this function)
External Power supply (SVGT008-166F only)
6A.4.1
GT3000 Identification
The drive configured for this function is identified with suffix 10. Ex. SVGT125FDNNNN10
Optional terminal board for external power supply
SVGT008-028F
SVGT200-780F
GT3000
Terminals
Terminals position
External power supply
SVGT008-028F
+S,
-, +,
+DC Bus
in the upper part near the net input terminals
GTAL230F1 (1000002621)
SVGT030-036F
+EBS, EBS
near the control board
GTAL230F1 (1000002621)
SVGT045-053F:
+EBS, EBS
Near the power input terminals
GTAL230F1L (1000090539)
SVGT066-108F
+EBS, EBS
near the control board
GTAL230F1L (1000090539)
SVGT125-166F
+EBS, EBS
near the control board
GTAL230F1 (1000002621)
SVGT200F-940M
L1F – L2F
in the upper part near the fan input terminals
It is configured like K/J series. External single-
phase power supply 230V.
Maximum cables section: 2,5 mm
2
, 14 AWG
NOTE:
1.
SVGT0P3/0P4/0P6: These drives are not available for external power supply.
2.
SVGT008-028:
The external power supply is in parallelwith the internal one. See connection diagram in the following pages.
3.
SVGT030-166:
External power supply is not in “OR” with the internal one, so it is necessary to handle the possible failure
of the external power supply, cutting the power supply of the coil of the main contactor with the Fault relay.
4.
The terEBS and -EBS must be connected to the ter and
of the external power supply
5.
The power supply GTAL230F1/GTAL230F1L has two internal fuses and it is suitable for one drive only.
6.
If the external power supply is out of order, the control switch off and the drive can't work. It's not possible to operate like a standard drive.
7.
If the control supply is external (parameter 06.09=External) the checks on the main power (under voltage, no grid, input phase loss, prech.
fault,...) are active with the drive enable closed only. The drive enable will be close after the turn on of the main power supply.
8.
Fault relay:
-SCADA BASIC control board: the relay RL1 cannot be used, because, in case of main power failure it will be de-energized, so it is
necessary to use one of the programmable digital outputs configured as "Drv Fault": on these outputs main supply protections do not have
effect until the “Drive Enable will be closed.
-SCADA PLUS control board: it is possible to use "drive fault relay RL1" because, if jumper JP19=open (see paragraph 3A.5.1), on that
output main supply protections do not have effect until the “Drive Enable will be closed.
It is possible to use the Fault relay (digital output sw.configured for SCADA BASIC or RL1 for SCADA PLUS) to command the main
contactor that, in this way, will be opened if the external power supply goes off during operation.
S
S
V
V
G
G
T
T
1
1
0
0
Drive arranged for external
power supply
Summary of Contents for GT3000
Page 1: ...GT3000 Hardware Software Manual www answerdrives com ...
Page 2: ......
Page 4: ......
Page 8: ...Table Of Contents GT3000 iv IMGT30017EN ...
Page 12: ...General Safety Precautions viii IMGT30017EN ...
Page 25: ...GT3000 Technical Data IMGT30017EN 13 Frames IV V VIN SVGT045 166 IP20 ...
Page 26: ...Technical Data GT3000 14 IMGT30017EN Frames IV V VIN SVGT045 166 IP54 ...
Page 28: ...Technical Data GT3000 16 IMGT30017EN Frames VII VIII IP00 SVGT200 521K SVGT200 470F ...
Page 29: ...GT3000 Technical Data IMGT30017EN 17 F series Frames 2xVII 2xVIII Parallel IP00 SVGT520 940M ...
Page 30: ...Technical Data GT3000 18 IMGT30017EN K series Frames 2xVII 2xVIII Parallel IP00 SVGT580 960K ...
Page 36: ...Installation GT3000 24 IMGT30017EN 3A 2 1 4 Frames VII VIII Installatiion ...
Page 58: ...GT3000 Installation 46 IMGT30004EN ...
Page 107: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 95 ...
Page 110: ...Terminal Boards and Power Schematics GT3000 98 IMGT30017EN ...