A2.4.3 Cabling
All control cables must be shielded. Control cable shielding prevents noise from entering control circuits.
The shield shall be grounded at the signal origin. Use a double-shielded twisted pair cable for analogue signals. This type of cable is recommended
for the pulse encoder signals also. Employ one individually shielded pair for each signal.
Do not use common return for different analogue signals.
A double-shielded cable is the best alternative for low-voltage digital signals but single-shielded twisted multipair cable is also usable.
A double shielded twisted
A single shielded twisted
pair cable
multipair cable
Run analogue and digital signals in separate, shielded cables.
Relay-controlled signals, providing their voltage does not exceed 48 V, can be run in the same cables as digital input signals. It is recommended that
the relay-controlled signals be run as twisted pairs.
Never mix 24 VDC and 115 / 230 VAC signals in the same cable.
•
Control signal cables must be
kept at a distance greater than
0.3m (1 foot) from power cables.
Keep both power cables and
signal cables in separate
raceways.
If it is necessary to cross power
and signal cables, cross at a 90°
(right) angle.
Figure A2.5.4.3 Cable Routing
Maximum section of control cables: 1,5mm
2
(AWG16)
A2.4.4 GROUNDING
For personnel safety, proper operation and to reduce electromagnetic emission/pickup, the drive and the motor must be grounded at the installation
site. Every drive shall have its own ground. A star ground system is acceptable although it is not the preferred method.
•
Conductors must be adequately sized as required by safety regulations.
•
Power cable shields must be connected to the drive PE terminal in order to meet safety regulations.
•
Power cable shields are suitable for use as equipment grounding conductors only when the shield conductors are adequately sized as required
by safety regulations.
•
In multiple drive installations, do not connect drive terminals in series.
•
The panel must have a properly sized ground bus to which all system grounds are connected. The bus bar shall be connected to plant ground.
•
Ground connections must be as short as possible.
•
The drive ground connection should not be shared with other devices.
•
High frequency RFI requires large areas of ground bus (due to skin effect).
SVGT/2
≥
0.3m
Crossing possible at 90°
≥
0.3m
Power cables
Control cables
Drive
a) Preferred connection
b) Acceptable connection
Drive
Drive
Drive
Drive
Drive
PE
PE
PE
PE
PE
PE
Summary of Contents for GT3000
Page 1: ...GT3000 Hardware Software Manual www answerdrives com ...
Page 2: ......
Page 4: ......
Page 8: ...Table Of Contents GT3000 iv IMGT30017EN ...
Page 12: ...General Safety Precautions viii IMGT30017EN ...
Page 25: ...GT3000 Technical Data IMGT30017EN 13 Frames IV V VIN SVGT045 166 IP20 ...
Page 26: ...Technical Data GT3000 14 IMGT30017EN Frames IV V VIN SVGT045 166 IP54 ...
Page 28: ...Technical Data GT3000 16 IMGT30017EN Frames VII VIII IP00 SVGT200 521K SVGT200 470F ...
Page 29: ...GT3000 Technical Data IMGT30017EN 17 F series Frames 2xVII 2xVIII Parallel IP00 SVGT520 940M ...
Page 30: ...Technical Data GT3000 18 IMGT30017EN K series Frames 2xVII 2xVIII Parallel IP00 SVGT580 960K ...
Page 36: ...Installation GT3000 24 IMGT30017EN 3A 2 1 4 Frames VII VIII Installatiion ...
Page 58: ...GT3000 Installation 46 IMGT30004EN ...
Page 107: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 95 ...
Page 110: ...Terminal Boards and Power Schematics GT3000 98 IMGT30017EN ...