The Preventing the recirculation of hot air
Outside the cabinet
Prevent hot air recirculation outside the cabinet by leading the
outcoming hot air away from the area where the inlet air to the
cabinet is taken.
Possible solutions are listed below:
- gratings that guide air flow at the air inlet and outlet
- air inlet and outlet at different sides of the cabinet
- cool air inlet in the lower part of the front door, and an extra
exhaust fan on the roof of the cabinet.
Inside the cabinet
Prevent hot air circulation inside the cabinet with leak-proof air
baffles as showed on the diagram on the right side.
No gaskets are usually required.
Figure 3A.3.1.2 Typical mounting.
NOTA
For IP54 version ask to
Technical department
Mounting Slot Locations
IP54 Mounting Complete
Bracket Move for Nema Mounting
Air outlet
Air inlet
Hot area
Air baffle plate
Cool area
Summary of Contents for GT3000
Page 1: ...GT3000 Hardware Software Manual www answerdrives com ...
Page 2: ......
Page 4: ......
Page 8: ...Table Of Contents GT3000 iv IMGT30017EN ...
Page 12: ...General Safety Precautions viii IMGT30017EN ...
Page 25: ...GT3000 Technical Data IMGT30017EN 13 Frames IV V VIN SVGT045 166 IP20 ...
Page 26: ...Technical Data GT3000 14 IMGT30017EN Frames IV V VIN SVGT045 166 IP54 ...
Page 28: ...Technical Data GT3000 16 IMGT30017EN Frames VII VIII IP00 SVGT200 521K SVGT200 470F ...
Page 29: ...GT3000 Technical Data IMGT30017EN 17 F series Frames 2xVII 2xVIII Parallel IP00 SVGT520 940M ...
Page 30: ...Technical Data GT3000 18 IMGT30017EN K series Frames 2xVII 2xVIII Parallel IP00 SVGT580 960K ...
Page 36: ...Installation GT3000 24 IMGT30017EN 3A 2 1 4 Frames VII VIII Installatiion ...
Page 58: ...GT3000 Installation 46 IMGT30004EN ...
Page 107: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 95 ...
Page 110: ...Terminal Boards and Power Schematics GT3000 98 IMGT30017EN ...