IMGT30017EN
1
Chapter 1A
GT3000 - OVERVIEW AND INSTALLATION FLOWCHART
1A.1 Overview
GT3000 drives have been designed for a wide range of applications and allow for the constant adjustment of motor speed. The GT3000 drives
are extremely compact, reliable, cost-effective, efficient and easy to use, and available for a wide range of three-phase motors. The state of the
art digital control allows extensive programming options.
The GT300 LARGE is developed for A.C. or D.C. power supply
GT3000 drives are suitable for single or multi-motor applications with asynchronous motors. Examples include the following:
•
Pumps – centrifugal, positive displacement, proportional
Fans – forced and induced draft, centrifugal, axial, evaporators
•
Mixers, agitators
Conveyors, conveyor belts, and packaging machines
•
Winders – films, paper, wire
Centrifuges
•
Extruders – melt pumps, pelletizers
Compressors
•
Machinery for paper, steel, and textile industries
Lifts, elevators, cranes and hoists.
They are available with 6 pulse (K), or 12 pulse (P), or 18 pulse (R) harmonic distortion, or AFE control.
Harmonic Comparison of a Typical 160 KW PWM 6, 12 and 18 pulse VFD vs. the GT3000 with Active front end operating from a 220KVA
5,75% impedance source.
Total Harmonic
Distortion
6-PULSE Harmonic
Waveform
12-PULSE Harmonic
Waveform
18-PULSE Harmonic
Waveform
ACTIVE FRONT END
(CURRENT) 30,1%
6,5%
2,5%
1%
(VOLTAGE) 8,1%
5,2%
2,9%
2,2%
1A.2
Notes about control modes
SCALAR CONTROL (V/F)
SENSORLESS CONTROL (without encoder)
VECTOR CONTROL (FOC) (with encoder)
Voltage frequency regulation with
constant or variable ratio variable
Independent torque and flow control
(= DC motor)
Independent torque and flow control
(= DC motor)
Voltage boost
Good static and dynamic performance
Excellent static and dynamic performance
Open-loop operation
Closed-loop operation (simulated)
Closed-loop operation
Limited speed regulation range: 1:15
Speed regulation range: 1:50
Speed regulation range: 1:1.000
Speed resolution: 1:1.000
Speed resolution: 1:5.000
Slip compensation
Typical static speed accuracy: 0.2 x fslip
(speed control range 5 - 100%:
<
0.2 %)
(speed control range below 5%:
≈
1 %)
Static speed accuracy: 0.01 %
Output current control
Torque control
Torque control also at zero speed
Torque control response: < 5 ms
Torque control response: 5 ms
Typical applications
Fans, centrifugal pumps, conveyor
belts, conveyors, roller conveyors
Extruder, presses, positive-displacement pumps Hoisting and lifting equipment, shearing machines,
coordinated devices
Summary of Contents for GT3000
Page 1: ...GT3000 Hardware Software Manual www answerdrives com ...
Page 2: ......
Page 4: ......
Page 8: ...Table Of Contents GT3000 iv IMGT30017EN ...
Page 12: ...General Safety Precautions viii IMGT30017EN ...
Page 25: ...GT3000 Technical Data IMGT30017EN 13 Frames IV V VIN SVGT045 166 IP20 ...
Page 26: ...Technical Data GT3000 14 IMGT30017EN Frames IV V VIN SVGT045 166 IP54 ...
Page 28: ...Technical Data GT3000 16 IMGT30017EN Frames VII VIII IP00 SVGT200 521K SVGT200 470F ...
Page 29: ...GT3000 Technical Data IMGT30017EN 17 F series Frames 2xVII 2xVIII Parallel IP00 SVGT520 940M ...
Page 30: ...Technical Data GT3000 18 IMGT30017EN K series Frames 2xVII 2xVIII Parallel IP00 SVGT580 960K ...
Page 36: ...Installation GT3000 24 IMGT30017EN 3A 2 1 4 Frames VII VIII Installatiion ...
Page 58: ...GT3000 Installation 46 IMGT30004EN ...
Page 107: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 95 ...