The distances of the aspiration apertures to each other and to
the wall of the duct are represented in the following table.
Bore distance
Duct cross section
≤
≤
≤
≤
0.5 m²
Duct cross section
> 0.5 m²
Distance from aspiration
apertures to wall
100 to 200 mm
200 to 300 mm
Distance of aspiration
apertures to one
another
100 mm
150 mm
Sampling aperture
diameter
The diameter of the sampling aperture results from the number of aspiration
apertures. The precise value can be found in Chapter 4.3.2 "Simplified pipeline
project planning”.
The pipe is concluded with an end cap without a bore.
Arrangement
The aspiration apertures should be arranged against the air flow.
During project planning, it is to be taken into account that the air conditioning
ducts for mounting the pipe system are often only accessible from two sides.
Example
The following illustration depicts two project planning examples of pipe systems
in air conditioning ducts.
Fig. 4.24: Ducts with small and large duct cross-section