Page 57
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
4.3.1.3 M-pipe system
1 pipe system
TITANUS
PRO·SENS
®
2 pipe systems
TITANUS
PRO·SENS
®
2
Fig. 4.31: M-shape pipe system for area protection
Limit values
Min. distance from TITANUS
to T-piece
4 m
Max. distance from TITANUS
to T-piece
20 m
Max. Branch length
with low fan voltage 6.5 V – 6.9 V
with high fan voltage 9 V – 12 V
30 m
40 m
Max. Overall pipe length per pipe system
with low fan voltage 6.5 V – 6.9 V
with high fan voltage 9 V – 12 V
110 m
140 m
Min. Distance between 2 aspiration apertures (d)
4 m
Max. Distance between 2 aspiration apertures (d)
12 m
Max. number of aspiration apertures (n) per pipe
system
12 pcs.