Page 62
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
4.3.2.2 U-pipe system
1 pipe system
TITANUS
PRO ·SENS
®
2 pipe systems
TITANUS
PRO ·SENS
®
2
Fig. 4.14: U-pipe system, e.g. for equipment protection
Limit values
Min. distance from TITANUS
to T-piece
2 m
Max. distance from TITANUS
to T-piece
20 m
Max. branch length
20 m
Max. overall pipe length Ø 25 mm
60 m
Max. number of aspiration apertures (n) per pipe system
18 pcs.
Minimum distance between aspiration apertures (d)
0.1 m
Maximum gap between aspiration apertures (d)
4 m
Aspiration apertures
Number of
apertures
2
4
6
8
10
12
14
16
18
∅
of all aspiration
apertures in mm
28
)
6.0
4.4
3.6
3.2
3.0
3.0
2.5
2.5
2.5
28