Page 5
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
•
The voltage can be set to 10 V, 11 V and 12 V with
the FC-3 fan control circuit board. The FC-3 fan control circuit board
available as an option for all TITANUS
PRO
·SENS
®
-SL devices.
1.2
Areas of Application
The air sampling smoke detection system TITANUS
PRO·SENS
®
is a smoke
detection system used for the early smoke detection and very early smoke
detection in rooms and equipment.
Principle
Air samples are drawn from the monitoring area via a pipe system with defined
air sampling points and passed to the detector module.
It is particularly suitable for areas in which point-type detectors cannot be used
or can only be used under certain conditions.
This applies in particular to areas: …
with difficult access and in which it is difficult to install or to maintain point-
type detectors.
which are air-conditioned.
which are higher than allowed for point-type detectors.
in which point-type detectors are not desired for aesthetic reasons.
in which electromagnetic fields have an impact .
which are exposed to high or low temperature.
with pollution of the air, where filter elements are needed.
which are jeopardized by vandalism.
Room protection
TITANUS
PRO·SENS
®
is suitable for the monitoring of rooms like
floor voids, ceiling voids
tunnels, ducts, voids difficult to access
storage areas, high-rack storage areas, elevator shafts
museums, cultural centre
deep-freeze storage areas
Fig. 1.1: Scheme - room monitoring with the air sampling smoke detection
system
TITANUS
PRO ·SENS
®