Page 4
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
1
Introduction
1.1
Features of the TITANUS
PRO·SENS
®
ASD System
TITANUS
PRO·SENS
®
is the latest generation of WAGNER air sampling smoke
detection systems. Besides its use for room and equipment protection the
variant can be used for monitoring climatic cabinets and climatic ducts.
Sensitivity
The device has a response sensitivity of up to 0.5 %/m, 0.1 %/m or 0.015
%/m
light obscuration. According to the application other sensitivities can be set.
Thanks to the innovative High-Power-Light-Source (HPLS) technology a wide
detection range over all rated fire types is guaranteed.
If two detector modules are inserted in the TITANUS
PRO·SENS
®
,
the
monitoring area is doubled.
LOGIC
·SENS
In order to prevent false alarms, the intelligent signal processing called
LOGIC
·SENS
distinguishes between interferences and the occurrence of real
fire.
Safe air flow monitoring
Like point-type detectors, which are electronically monitored to detect line
fractures and short circuits, air sampling systems require a complex and safe air
flow monitoring. The unique air flow sensor technology used in all WAGNER air
sampling smoke detection systems guarantees the detection of faults such as
pipe fracture or blockage of air sampling points.
The air flow monitoring is temperature compensated and can be independent of
the air pressure.
Patented air sampling
points
Depending on the required pipe design the air sampling points have specified
hole diameters. For these air sampling points WAGNER has developed
patented
aspiration-reducing film sheets
with marking tape and clips that
allow easy mounting and avoid secondary noise. The diameter of the air
sampling point is clearly marked on the film sheets, allowing quick and easy
checking of the air sampling point diameter.
Point detector spacing
The air sampling points of the system can be compared to point-type detectors.
The monitoring areas comply with the valid national regulations.
Diagnostics software
The diagnostic software permits a quick and reliable fault localization for
maintenance and service. The current and memorized device state can be read
by a PC via a special cable.
Choice of ventilator
voltage
The fan voltage can be set according to project planning via plug-in jumpers.
With TITANUS
PRO
·SENS
®
devices, the fan voltage can be set between 6.9 V
and 9 V by means of the jumpers on the base board.
The voltage with TITANUS
PRO
·SENS
®
devices can be set by means of the
fan control circuit boards FC-2 and FC-3.
•
The voltage can be set to 6.5 V, 6.9 V and 9 V with the FC-2 fan control
circuit board. The FC-2 fan control circuit board is standard in all
TITANUS
PRO
·SENS
®
-SL devices.