Page 106
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
6.4
Monitoring in forced air flow systems
(ventilation or climatic applications)
6.4.1
Detection at air inlets/outlets
If aspiration takes place in a forced air flow system (ventilator, climatic
systems), the air sampling points must be positioned in the air flow. Place
the air sampling points as shown in fig. 6.5.
Fig. 6.5: Positioning of air sampling point, depending on air speed
6.4.2
Detection in bypass systems
In case of detection with air flows
≥
2 m/s the outgoing air of the
TITANUS
PRO · SENS
®
is additionally to be returned to the air flow area.
The end of the air return pipe is to be cut in an elbow of 45° (refer to Fig.
6.6)
For the air return connection please refer to chapter 6.6 "Air Return".
Fig. 6.6: Positioning of air return, example of a climatic duct (bypass)
For the pipe design of TITANUS
PRO·SENS
®
in these areas refer to chapter
4.7 "Pipe Design for Forced Air Flow".