7.2
Detector module and alarm transmission
Trigger the alarm of the detector module and check the transmission to the
central fire panel as follows:
1. Spray test aerosol either into the first air sampling point or into the test
adapter of the pipe system of TITANUS
PRO·SENS
®
.
2. Follow the steps in the table.
Check whether ...
If this is not the case ...
the air sampling smoke detection
system displays an alarm.
1. check whether the display board is
connected.
2. the air sampling system is damaged.
3. exchange the detector module.
the alarm signal is transmitted to
the central fire panel and on the
corresponding line.
1. check the transmission cables.
If the
LOGIC
·SENS
switch S1-10 is set to "ON" (refer to chapter 5.3
"Settings"), it should be set to "OFF" for the alarm triggering test through
test aerosol in order to accelerate the alarm processing.
Record all checked data in the inspection protocol.