Page 90
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
5.6.1
Connection to F.D.C.I.E. , with reset button
The relay contacts on the base board can be used to e.g. connect TITANUS
PRO·SENS
®
to a fire detection control and indicating equipment, to trigger
signalling devices, security management systems etc. It is also possible to
connect a response indicator.
The reset input must not be permanently connected to +24V. Otherwise all
signals – even an alarm – are automatically reset after the cause of the
signal has been eliminated. In this case the alarm is non-latched.
Fig. 5.11: Example of the connection of
TITANUS
PRO·SENS
®
with fire
detection control and indicating equipment and reset button
INSTRUCTION