Page 69
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
If it is absolutely necessary to attach the pipe system directly
behind baffles, sound suppressers or angles, the main flow
speed areas will have to be monitored (see Fig. 4.19/20).
Fig. 4.20: Change in direction of a duct
without
baffles
Fig. 4.21: Sound suppressors in a duct
The following must be taken into consideration when installing a pipe system in
air conditioning ducts:
•
Air recirculation (see following page) should be planned for, since the
TITANUS
PRO·SENS
®
and the pipe system are located in different
pressure areas.
•
The pipe inlets in the duct must be sealed so that they are air tight.
•
The part of the pipe system located outside of the duct must be sealed so
as to be air tight.