background image

 

30308679

         

                                                                                               

                     

  Issue 1.04

 

                                       

 

 

Features 

 

Sensitivities programmable. 

 

Strong 

environmental 

adaptability 

due 

to 

drift 

compensation. 

 

Integrated  algorithm  for  analyzing  fire,  improving  the 
sensitivity highly.   

 

Self-diagnostic. 

 

Reed switch testing. 

 

Removable  innovative  sensing  chamber,  easy  for 
maintenance. 

 

Reporting dirt fault for contaminated chamber. 

 

Fire LED allows 360

°

viewing. 

 

3-level sensitivities and fixed temperature or rate of rise 
programmable.   

Description 

DC-9101 (IS) Intrinsically Safe    Conventional    Combination 
Heat 

Photoelectric 

Smoke 

Detector 

(the 

detector), 

non-addressable, is a kind of combination detector consisting 
of  smoke  sensing  parts  and  semi-conductor  heat  sensing 
parts  in  technological  structure  and  circuit  structure.  It’s 
applicable to zone 1 and zone 2 of areas with explosion-proof 
requirement  in  petroleum  and  chemical  industries.  It  can 
match  with  fire  alarm  control  panel,  I-9332  Interface, 
explosion-proof detector and end-of-line resistor produced by 
GST  to  conduct  the  processing  of  detector  signals.  The 
detector  has  the  advantages  of  both  conventional 
photoelectric detector and rate of rise and fixed temperature 
heat  detector.  Just  because  of  the  combination  of  smoke 
detector  and  heat  detector,  it  overcomes  the  non-sensitivity 
to  dark  smoke  particles  of  ordinary  scattering  photoelectric 
detectors.  It  can  also  pick  up  fire  with  obvious  rise  of 
temperature  such  as  alcohol  flame,  thus  extending  the 
application range. 

Connection and Cabling 

Fig.1 shows the detector bottom and Fig. 2

 

the base. 

A

 

C

B

100mm

A

 

Fig. 1                                Fig. 2

 

There are four terminals with numbers on the base. 

1: Detection zone positive IN 
2: Detection zone positive OUT 
3: Detection zone negative IN and OUT 
4: No connection.

 

Recommended Cabling 

1.0mm

or  above  fire  cable.  The  capacitance  distributed 

among  cables  should  not  be  over  0.083

μF,  and  the 

inductance  distributed  should  not  be  over  4.1mH.  Laid  out 
through  metal  conduit  or  flame-retardant  conduit,  subject  to 
local codes.   

Installation 

 

Fix the base with two tapping screws, and then align mark A 
on the detector bottom with B on the base, rotate the detector 
to  align  mark  A  with  mark  C  (Refer  to  Fig.  1  and  2  for  the 
position of the marks), the detector will be fitted to the base. 

 

 

Fig.3 shows the mounting of the detector. 

 

 

 

 

Fig. 3 

Application 

Warning: The alarm current depends on the current limit 
of  the  control  panel.  24VDC  cannot  power  the  detector 
directly. Otherwise the detector will be blown up for lack 
of current limit resistor.

 

The sensitivity level 1 is defaulted, which can be modified by 
P-9910B  programmer.  Refer  to  P-9910B  Hand  Held 
Programmer Installation and Operation Manual for details. 
In power-on state, input unlocking password and press 

Clear

 

to unlock. Press 

Function

, then number 

“3”, the screen shows 

“-” at the last digit.   

Note:  Programming  should  be  done  in  safety  zones 
because 

handheld 

programmers 

belong 

to 

non-intrinsically safety devices.

 

Input  corresponding  sensitivity  or  parameter  and  press 

Program

,  the  screen  will  show  a  “P”,  the  corresponding 

sensitivity or parameter is programmed. Press 

Clear

 to clear 

the "P". Input locking password and press 

Clear

 to return. 

Rate of rise and level 1 is defaulted.   

Parameters set using programmer 

Input Number   

Smoke Sensitivity 

Heat Sensitive   

Level 1 

Rate of rise 

Level 2 

Rate of rise 

Level 3 

Rate of rise 

11 

Level 1 

Fixed temperature 

12 

Level 2 

Fixed temperature 

13 

Level 3 

Fixed temperature 

If the detector connects  with fire alarm control panel, I-9332 
interface  and  other  exposition  proof  products  in  series,  a 
4.7k

Ω

 end-of-line resistor should be connected to the end of 

loop. System connection is shown in Fig. 4. Note the polarity 
of power line.   

 

 

 

 

 

Fig. 4 

The  interface  is  integrated  with  a  safety  barrier,  which  shall 
be installed in safe area. The total number of explosion-proof 
devices connected in the system shall not be over 10. 
Safety Barrier Parameters

Uo

28V

Io

93mA

Co=0.083uF

Lo=4mH

Po=651mW

Explosion-proof Mark: 

[Exi[ExibGb] IIC

Explosion-proof Certificate Number: 

DC-9101(IS) Intrinsically Safe 

Conventional Combination Heat Photoelectric Smoke Detector

 

 

4

2

3

1

Z

e

n

e

Bar

ri

e

r

O-

O+

Z2

Z1

D2

D1

Ci

rc

u

it

 Bo

a

rd

I- 9332 Interface 

End o

f line

 re

sist

or

4.

7k

Ω

Hazardous Area

Safety Area 

......

  

DC-9101 (IS) Intrinsically Safe  Conventional

Combination Heat Photoelectric Smoke Detector

  

DC-9101 (IS) Intrinsically Safe  Conventional

Combination Heat Photoelectric Smoke Detector

  

DC-9101 (IS) Intrinsically Safe  Conventional

Combination Heat Photoelectric Smoke Detector

Detector

Base

Conduit

Back Box