Page 122
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
7.3
Check air flow monitoring
Pipe Fracture
Verify the detection of a pipe fracture:
1. Loosen the connection between the pipe and TITANUS
PRO·SENS
®
or open
the test adapter.
2. Verify whether the fault display of the air sampling smoke detection system is
lit.
3. Check optionally the data of the air flow sensor using the diagnostic software
DIAG 3 and a PC or laptop.
4. Register the result in the commissioning protocol.
Blockage
Verify the detection of a blockage:
1. Close the necessary number of air sampling points by means of adhesive
tape according to the chosen configuration of the air flow monitoring.
2. Check whether the fault display of the air sampling smoke detection system
is lit.
3. Check optionally the data of the air flow sensor using the diagnostic software
DIAG 3 and a PC or laptop.
4. Register the result in the commissioning protocol.
A pipe fracture or blockage is indicated by a flash code via the LED of the
detector module.
- fracture: 3x flashing
- blockage:
2x flashing
The corresponding flash code is repeated every two seconds.
Trouble Shooting
If faults in the air flow are not correctly detected by the device do the following:
Check whether ...
1. all air sampling points are free.
2. the pipe system has fractures or cracks.
3. all pipe connections are tight.
4. the ventilator is unblocked.
5. the correct aspiration-reducing film sheets have been used.
If no faults are detected the functionality of TITANUS
PRO·SENS
®
or the air
flow sensor is checked by means of the test pipe or through the diagnostic
software (refer to chapter 7.5 "Operational Check TITANUS
PRO·SENS
®
")
.
INSTRUCTION