Page 11
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
Relay output
TITANUS
PRO·SENS
®
possesses a potential-free change-
over contact for the existing alarm threshold and the collective
fault . Thus, the air sampling smoke detection system can be connected to the
addressable
2
detection lines of any fire detection control and indicating
equipment (F.D.C.I.E.).
Air flow adjustment
The air flow of TITANUS
PRO·SENS
®
is automatically adjusted so that
commissioning is much easier. The initialization is effected dependently on or
independently of the air pressure.
In order to adjust the TITANUS
PRO·SENS
®
a characteristic air flow of the pipe
network the air flow-init process is affected. For each device this process is
necessary one time after the installation, after each modification of the pipe
system design and after the modification of the ventilator voltage. Thus the
device determines and memorizes the air flow characteristic of the pipe
network.
Pipe system
A pipe system up to a total length of 300 m with a maximum number of 32 air
sampling points can be connected to TITANUS
PRO·SENS
®
.
Two pipe systems can be connected to TITANUS
PRO·SENS
®
2. The whole
pipe system then measures 2 x 280 m and has a maximum of 2 x 32 aspiration
points.
2
Only possible via addressable I/O modules of the fire detection control and indicating equipment
(F.D.C.I.E.).