background image

 

 

 

 

ALL-SPEC_Unit_HON.doc 07/2011 

1/9 

 

Installation Instructions for 
Honeywell ALL-SPEC Air Sampling Smoke Detection System 

 

 

 

Operating indicator light 

Alarm indicator light for detector  
module II 

Alarm indicator light for detector  
module I 

Indicator light for common fault 

Pre-punched cable entries for connection to the central fire panel or power supply (input/output) 

Connection pipe system I 

7 Connection 

pipe 

system II 

Connection for air return 

 

8

 

5

 

5

 

1

2

6

7

5

3

4

Summary of Contents for ALL-SPEC

Page 1: ...tor light 2 Alarm indicator light for detector module II 3 Alarm indicator light for detector module I 4 Indicator light for common fault 5 Pre punched cable entries for connection to the central fire panel or power supply input output 6 Connection pipe system I 7 Connection pipe system II 8 Connection for air return 8 5 5 1 2 6 7 5 3 4 ...

Page 2: ...stic cover Take for this if necessary a screwdriver 5 Break carefully the clasp for the connection of the second pipe system predetermined breaking point marked by II with a screwdriver from the housing Note The knocked clasp is to removed completely from the device 6 Make the required settings at the detector module by setting the contacts of switch S1 accordingly see also Settings of the detecto...

Page 3: ... 06 m off on 1 0 m 0 2 m 0 03 m on off 0 5 m 0 1 m 0 015 m off off Setting the alarm delay S1 3 S1 4 0 seconds off off 10 seconds on off 30 seconds off on 60 seconds on on Setting the activating threshold air flow fault S1 5 S1 6 I on off II off on III off off IV on on Setting the delay air flow fault S1 7 S1 8 0 5 minutes off on 2 minutes on off 15 minutes on on 60 minutes off off Setting the fau...

Page 4: ... jumper must be put or not X pin pair bridge O pin pair open The standard settings have a grey background Choose number of the detector modules Jumper Pin No JU4 1 2 1 detector module X 2 detector module O Setting the ventilator voltage Jumper JU1 allows to set the ventilator voltage on the base board The following table shows whether the jumper is set or not X pin pair bridged O pin pair open The...

Page 5: ...odule I Jumper JU2 Fault contact detector module II Jumper JU3 The following table shows the positioning of the jumpers X pin pair bridge O pin pair open The standard settings have a grey background Setting the collective fault contact Jumper Pin No JU2 3 1 2 JU2 3 2 3 break contact X O make contact O X A B Device Supports A B Support type MT 1 horizontal installation Support type MT 1 vertical in...

Page 6: ... jig Fix the device using four screws max of 6 mm for wall mounting and max of 4 mm for mounting by means of the device support MT 1 in order to guarantee a safe fixing and to limit vibrations which occur 2 Fix the device by means of four screws in accordance with the mounting type to the wall or the device support Make sure the device is not fixed under mechanical tension or the screws are not ti...

Page 7: ... relay break contact X6 4 X6 5 external response indicator for first detector module external response indicator for first detector module X6 6 X6 7 24 V reset input 0 V reset input X6 8 X6 9 24 V supply voltage 0 V supply voltage X7 1 X7 2 fault contact 2nd detector module connection 1 fault contact 2nd detector module connection 2 X7 3 X7 4 X7 5 contact of the 2nd alarm relay make contact centre...

Page 8: ...it button S2 see figure of the corresponding detector module until the green operating indicator light of the device starts flashing The initialization is terminated after approx 5 seconds After a successful initialization the operating indicator light is lit permanently 3 During and after initialization the pipe system must no longer be changed Even the ventilator voltage of the device must no lo...

Page 9: ...n issued by notified product certification body ID no 0786 VdS The CE designation according to DIN EN 54 20 has been carried out 0786 WAGNER Group GmbH Schleswigstrasse 1 5 30853 Langenhagen 09 Nr 0786 CPD 20685 EN 54 20 2006 Air sampling smoke detector for fire detection and fire alarm systems in buildings 0 015 light obscuration m Class A B and C 0 1 light obscuration m Class A B and C 0 5 light...

Reviews: