background image

HW-500-003 

I56-3934-002R

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Models:  5193SD, 5193SDT
Addressable Photoelectric Smoke Detector

BEFORE INSTALLING

Before  installing  detectors,  please  thoroughly  read  the  supporting 

Honeywell control panel installation instructions, which provide de-

tailed information on detector spacing, placement, zones, and special 

applications. Copies of the installation instructions are available from 

Honeywell. NFPA 72 and NEMA guidelines should also be observed.

NOTICE

:

 This manual shall be left with the owner/user of this equipment.

IMPORTANT

:

 This detector must be tested and maintained regularly follow-

ing NFPA 72 requirements. At a minimum, cleaning should be performed an-
nually.

GENERAL DESCRIPTION

The  Model  5193SD/SDT  addressable  photoelectric  smoke  detector  incorpo-
rates a state-of-the-art optical sensing chamber and an advanced microproces-
sor.  Built-in  Drift  Compensation  algorithms  automatically    maintain  proper 
operation at factory calibrated detection levels, even when sensitivity  is al-
tered due to the presence of contaminates settling into the unit’s chamber. In 
order for this feature to work properly, the chamber must never be opened 
while power is applied to the smoke detector. This includes cleaning, mainte-
nance or screen replacement. Should it become necessary, the screen/sensing 
chamber is field replaceable.  Once the detector has reached its limit of com-
pensation, a maintenance signal  is indicated at the panel. The 5193SDT also 
features a restorable, built-in, fixed temperature (135°F) thermal detector.

The detector is designed to provide open area protection and to be used with 
compatible UL-listed Honeywell control panels.

Installation of the 5193SD/SDT detector is simplified by the use of a mounting 
base that may be pre-wired to the system, allowing the detector to be easily 
installed or removed. 

Two LEDs on the detector provide a local visual indication of the detector’s 
status: 

TABLE 1: DETECTOR LED MODES

Green LED

Red LED

Power-up

Blink 10 sec

Blink 10 sec

Normal (standby)

Blink 5 sec

Out of sensitivity

Off

Blink 5 sec

Heat Sensor Trouble Off

Blink 10 sec

S m o k e / T h e r m a l  
Alarm

Off

Solid-(Initiating 
device only)
Blink 1 sec

During  initial  power-up,  the  red  and  green  LEDs  will  blink  synchronously 
once every ten seconds. It will take approximately 50 seconds for the detector 
to finish the power-up cycle (see Table 2).

TABLE 2: POWER-UP SEQUENCE FOR LED STATUS INDICATION

Condition

Duration

Initial LED Status Indication

approx.14seconds

Initial LED Status Indication
(if excessive electrical noise is present)

4 minutes

NOTE

:

 If, during power-up, the detector determines there is excessive electri-

cal noise in the system such as those caused by improper grounding of the 
system or the conduit, both LEDs will blink for up to 4 minutes before display-
ing detector status (see Table 2).
After power-up has completed and the detector is functioning normally within 
its listed sensitivity range, the green LED blinks once every five seconds. If the 
detector is in need of maintenance because its sensitivity has shifted outside 
the listed limits, the red LED blinks once every five seconds. When the detec-
tor reports an alarm condition to the control panel, the panel will send a code 
command to steadily light that unit’s red LED.  If the same loop has multiple 
detectors reporting alarm, only the first detector that reported alarm would 
have  have  its  red  LED  turned  on  steadily.      The  remaining  units  in  alarm 
will blink their red LED once per second.  However, the panel will latch the 
address of all detectors that reported alarm. The LED indication must not be 
used in lieu of the tests specified under 

Testing

.

 

To measure the detector’s sensitivity, the Model SENS-RDR Infrared Sensitivity 
Reader tool (see Figure 5) should be used.

PROGRAMMING

The 5193SD/SDT has an internal serial number which must be enrolled in the 
control panel prior to its use in the system. Before programming, make sure 
the detector is mounted on its base. To program this device, enter the control 
panel’s Zone Programming mode. Assign the appropriate Fire Zone Type and 
an Input Type of “06” (serial number polling loop device). When prompted, 
either press the “test” button on the smoke detector to enroll the serial num-
ber (it will be displayed on the keypad), or enter the serial number manually 
through the keypad. Press the “test” button again to enroll the loop number, 
or enter loop number “1.”

MOUNTING

Each  5193SD/SDT  detector  is  supplied  with  a  mounting  base  that  can  be 
mounted:

1.  Direct mount or to ceiling using drywall fasteners (Figure 1).
2.  To a single gang box, or
3.  To a 3 

1

/

2

-inch or 4-inch octagonal box, or

4.  To a 4-inch square box with a plaster ring

I

56-3934-00

2R

SPECIFICATIONS

 

5193SD, 5193SDT
Heat Sensor: (Model 5193SDT): 

135°F (57.2°C); Fixed Temperature Electronic Thermistors

Operating Ambient Temperature Range:  32 to 100°F (0 to 38°C)
Operating Humidity Range: 

0 to 95% RH non-condensing

Storage Temperature Range: 

–4 to 158°F (–20 to 70°C)

Diameter (including base): 

5.3 inches

Height (including base): 

2.0 inches 

Weight: 

6.3 oz.

Agency Listing:  

UL-268

System Voltage Range:  

7-14V

Standby Current (maximum @ 12V)
LED off:  

1.2mA

LED on: 

2.8mA

Reviews: