Impulse™ Series
64
4.8 Byte Ordering
Data can be accessed as integers (16 bits), long integers (32 bits), and
floating point value (32 bits). The order that the bytes are sent must be
known by the master in order to assembly the bytes into the correct value.
Byte ordering can have a few different terminologies.
1) Big/Little Endian
2) Byte order by number, with 1 indicating the most significant part of
the value, and 4 the least significant,
3) Word/Byte, indicating which word (16 bits, high or low) is sent first,
and which byte of the word (high or low) come first in that byte.
See the following example for accessing a product reading of 46.60 inches.
The integer value will be 4660, which translates to the hex number
0x00001234. The individual bytes, 0x00, 0x00, 0x12, and 0x34 can be
sent the following 4 ways for 32 bits values:
1) Big Endian, Byte order 1234, High Word High Byte (HWHB)
Order sent: 0x00, 0x00, 0x12, 0x34
2) Little Endian, Byte order 4321, Low Word Low Byte (LWLB)
Order sent: 0x34, 0x12, 0x00, 0x00
3) Big Endian Byte Swapped, Byte order 2143, High Word Low Byte (HWLB)
Order sent: 0x00, 0x00, 0x34, 0x12
4) Little Endian Byte Swapped, Byte order 3412, Low Word High Byte (LWHB)
Order sent: 0x12, 0x34, 0x00, 0x00
The individual bytes 0x12, and 0x34 can be sent the following 2 ways for
16 bits values:
1) Big Endian, Byte order 12, High Byte first (HB)
Order sent: 0x12, 0x34
2) Little Endian, Byte order 21, Low Byte first (LB)
Order sent: 0x34, 0x12
4.9 Enron Modbus
Enron Modbus has a few differences from Traditional Modbus. One
difference is the register offsets follow a different numbering scheme,
with integer values residing in the 3XXX range, long integers in the 5XXX
range, and floating points in the 7XXX range. The second difference is
that 32 bits of data can be returned in one register.
The Impulse supports both of these features, by selection of the proper
register value.
Summary of Contents for Impulse GW Series
Page 4: ...Contents...
Page 6: ...Section 1...
Page 16: ...Section 2...
Page 25: ...Installation 19 2 6 Dual Compartment Housing...
Page 26: ...Section 3...
Page 56: ...Section 4...
Page 82: ...Impulse Series 76 5 2 1 System Dimensions Continued...
Page 83: ...Supplementary ATEX Installation Instructions 77 5 2 1 System Dimensions Continued...
Page 84: ...Impulse Series 78 5 2 1 System Dimensions Continued...
Page 86: ...Section 6...
Page 92: ...Section 7...
Page 93: ...Control Drawings 87 Section 7 Control Drawings 7 1 FM FMC Control Drawings...
Page 94: ...Impulse Series 88 7 1 FM FMC Control Drawings Continued...
Page 95: ...Control Drawings 89 7 2 ATEX Control Drawings...
Page 96: ...Impulse Series 90 7 2 ATEX Control Drawings Continued...