Impulse™ Series
26
3.3 Configuration Menu (Continued)
Fct. 1.06 Upper
Dead Zone
(UP DZ)
Specifies the distance from the
sensor mounting in which no
measurement takes place. Preset
based on sensor type and typi-
cally not edited.
May be of use to minimize re-
flections from mountings not in
conformance with recommended
practices.
Must be set above URV (level
or volume) or LRV (distance) to
achieve full 4 - 20 mA range.
When level is tracked into the
Upper Dead Zone the output
will change to the error current
specified in Fct A.09, Near Zone
Output, and remain there until
level falls backs into the measur-
able range.
NOTE: If the system is powered
on or “signal acquire” is activated
with the level in the Upper Dead
Zone, it will not be detected and
an erroneous reading may result.
Changing Material Type, Fct.
1.05, or Probe Type, Fct A.06,
will reset this function to factory
default values.
Editing this function changes
Material Type, Fct 1.05, to “CUS-
TOM”
User editable
value
Default depen-
dent Probe Type
and Material Type
Increase value
from factory set-
ting as required.
Do not decrease
value below
factory setting
without factory
consultation.
Fct 1.05: Material
Type
Summary of Contents for Impulse GW Series
Page 4: ...Contents...
Page 6: ...Section 1...
Page 16: ...Section 2...
Page 25: ...Installation 19 2 6 Dual Compartment Housing...
Page 26: ...Section 3...
Page 56: ...Section 4...
Page 82: ...Impulse Series 76 5 2 1 System Dimensions Continued...
Page 83: ...Supplementary ATEX Installation Instructions 77 5 2 1 System Dimensions Continued...
Page 84: ...Impulse Series 78 5 2 1 System Dimensions Continued...
Page 86: ...Section 6...
Page 92: ...Section 7...
Page 93: ...Control Drawings 87 Section 7 Control Drawings 7 1 FM FMC Control Drawings...
Page 94: ...Impulse Series 88 7 1 FM FMC Control Drawings Continued...
Page 95: ...Control Drawings 89 7 2 ATEX Control Drawings...
Page 96: ...Impulse Series 90 7 2 ATEX Control Drawings Continued...