Command Block 3: Program Limit Setpoints (continued)
Command Word Bits (continued)
Bits 10-13:
Program associated limit switch setpoint pair. If the bit is set to ‘1’, program the setpoint pair
with the data in the associated words of the command block. If the bit is reset to ‘0’, ignore the
data in the associated words. See
below for a description of the
programming data format.
Bit 14: Apply LS Preset Value.
When this bit is set to ‘1’, the Limit Switch Position will be set to the pro-
grammed LS Preset Value. The LS Preset Value has a default value of zero. If bit 9 of the command
word is also set to ‘1’, the Limit Switch Position will be set to the value in word 3 of this block.
When this bit is reset to ‘0’ the Limit Switch Position will not be changed.
LS Setpoint Pair Data Format
Words 4 through 19 are used to program the four limit switch setpoint pairs associated with the output point
designated by word 1 of the command block. Note that you do not have to program four setpoint pairs on
each output. The number of setpoint pairs programmed for the output is controlled by bits 10 through 13 in
the command word.
To program one setpoint pair, set bit 10 in the command word and put data in words 4 through 7.
To program two setpoint pairs, set bits 10 and 11 and put data in words 4 through 11.
To program three setpoint pairs, set bits 10 through 12 and put data in words 4 through 15.
To program four setpoint pairs, set bits 10 through 13 and put data in words 4 through 19.
1) When the FROM and TO Setpoints are equal and non-zero, and the Stitch Distances are set
to zero, the output will always be on.
2) Setpoint pairs cannot overlap. A programming error occurs if they do.
Pair 1
Word
Pair 2
Word
Pair 3
Word
Pair 4
Word
Parameter
Range
4
8
12
16
FROM Setpoint
0 to (
Full Scale Count
-1)
5
9
13
17
TO Setpoint
0 to (
Full Scale Count
-1)
6
10
14
18
ON Stitch Distance
0 to ignore.
See
for calculating ON Stitch Distance
7
11
15
19
OFF Stitch Distance
0 to ignore.
See
for calculating OFF Stitch Distance
Summary of Contents for ANS1 ANYNET-I/O
Page 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0A090...
Page 6: ...Table of Contents ADVANCED MICRO CONTROLS INC 6 Notes...
Page 26: ...Limit Switch Functionality ADVANCED MICRO CONTROLS INC 2 26 Notes...
Page 36: ...Additional Functionality ADVANCED MICRO CONTROLS INC 3 36 Notes...
Page 90: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...