20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254 Fax: (860) 584-1973 http://www.amci.com
Installing the ANS1
4
51
I/O Wiring (continued)
ANSI Outputs
The ANS1 has outputs 9 through 16 available on the I/O connector. These are 12 to 24Vdc sourcing outputs.
All eight outputs share the single power supply, which must be connected to the “+Vdc In” pin shown in fig-
ure 4.17 below.
Figure 4.17 ANS1 Output Wiring
1) The “+Vdc In” pin carries the current for all of the outputs. The connector is rated for a max-
imum of eight amps per pin, and a 16 AWG wire should be used to connect this pin to the
power supply.
2) Overloading any of the outputs will trip the internal resettable fuse, which will temporarily
disable all eight outputs.
3) All inductive loads must have surge suppression devices installed on their input terminals.
Repeated high voltage spikes on the outputs of the ANS1 may permanently damage them.
+12 Vdc to +24 Vdc
Power Supply
DC Load
DC Load
11
10
9
8
7
6
5
4
3
2
1
11
10
9
8
7
6
5
4
3
2
1
ANS1 TOP VIEW
Right Connector Only
(Above Indicator LED’s)
J2
J1
Not Used
Common
+Vdc In
Out 9
Out 10
Out 11
Out 12
Out 13
Out 14
Out 15
Out 16
Not Used
Shield
Not Used
In 9
In 10
In 11
In 12
In 13
In 14
In 15
In 16
16 AWG Wire
All DC inductive loads must
have surge suppression devices
installed on their input terminals
Summary of Contents for ANS1 ANYNET-I/O
Page 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0A090...
Page 6: ...Table of Contents ADVANCED MICRO CONTROLS INC 6 Notes...
Page 26: ...Limit Switch Functionality ADVANCED MICRO CONTROLS INC 2 26 Notes...
Page 36: ...Additional Functionality ADVANCED MICRO CONTROLS INC 3 36 Notes...
Page 90: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...