Chapter 4 Parameter Index
86
Function
code
Parameter name
LCD display
Setting range
Setup
Modif
ication
MODBU
S address
installing braking
resistor)
1: Allowed
Pd.11
Overvoltage stall
point
Overvoltage stall
point
3004GB and below: 110.0
~ 150.0% of the bus
voltage
35R5GB and above:
120.0 ~ 150.0% of the
bus voltage
220V
models:
120%
380V
models:
140%
×
0E0B
Pd.12
Input default
phase detection
reference
Input default
phase detection
reference (100%
corresponds to
800V)
1~100%
100%
×
0E0C
Pd.13
Input default
phase detection
time
Input default
phase detection
time
2~255s
10s
×
0E0D
Pd.14
Output default
phase detection
reference
Output default
phase detection
reference (100%
corresponds to
rated current of
the motor)
0~100%
0%
×
0E0E
Pd.15
Output default
phase detection
time
Output default
phase detection
time
0.0~2.0s
0.2s
×
0E0F
Pd.16
Keypad keys
UP/DN
activation
Keypad keys
UP/DN
activation
0: Invalid
1: Activation
0
×
0E10
Pd.17
AE1, AE2, AE3
alarm selection
AE1, AE2, AE3
alarm selection
0: Do not display warning
1: Display warning
0
×
0E11
Pd.18
Number of
automatic reset
times
Number of
automatic reset
times
0-10, 0 indicates no
automatic reset
Only three failures have
automatic reset function
0
×
0E12
Pd.19
Reset interval
time
Reset interval
time
2.0~20.0s
5.0s
×
0E13
Pd.20
Confirm the time
before
deceleration due
to overcurrent
Confirm the time
before
deceleration due
to overcurrent
0~200ms
50ms
×
0E14
Pd.21
Run protection
while powering
on
Run protection
while powering
on
0: Not protect
1: Protect
0
○
0E15
Pd.22
Run protection
after switching
the run
command set
mode
Command to
switch run
protection
0: Continue to run
1: stop, received a new
run command
Re-run after the
command
0
×
0E16
Pd.23
Action selection
in case of stall
(reserve)
Anti-stall action
selection
0: Do not execute
anti-stall action sequence
1: Execute anti-stall
action sequence
0
×
0E17
Pd.24
Stall action
toggle condition
Stall action
toggle condition
0: The output current
exceeds the toggle
level
2
×
0E18