Chapter 2 Installation and Wiring
19
Catego
ry
Terminal
label
Name
Description of terminal
function
Specification
output terminal Y1
multi-function output
terminal Y1
leaving the factory
Internal isolation between CME and
GND
CME1
Common port of
output terminals
Y2~Y3 of IO
extension board
Common port of
multi-function output
terminals Y2~ Y3
Isolated to GND, and short connected
with COM1 while leaving the factory
PE
Shield ground
It is used for grounding of
terminal wiring shield layer.
Shield layer of analog signal
lines, 485 communication
lines, and motor cables can be
connected to this terminal
It is internally connected to connection
terminal PE of major loop
2.5.2 Wiring of control circuit terminals
●Wiring of analog input terminals
AI1/AI2 terminals accept analog signal input, toggle switches SW1 and SW3 select the input voltage (0 ~ 10V) or
the input current (0 ~ 20mA). AI3 (exclusive for 35R5GB and above models) terminals accept analog signal input,
toggle switch SW4 selects the input voltage ( - 10 ~ 10V) or the input current (-20 ~ 20mA). The wiring of terminals
is shown in Fig. 2-14:
AI1/AI2 0-10V/0-20mA
AI3 -10-10V/-20-20mA
AI1 AI2 AI3
GND
PE
Near-end of shield
line is grounded
I
V
SW1/SW3/SW4
Inverter
Fig. 2-14 Wiring diagram of analog input terminals
●
Wiring of analog output terminal
In S2R4GB ~ 3004GB, analog output terminal AO1 external connecting analog meter can indicate a variety of
physical quantities. Slide switch SW2 selects the output voltage (0/2 ~ 10V) or the output current (0/4 ~ 20mA). The
wiring of terminals is shown in Fig. 2-15:
Fig. 2-15 Wiring diagram of S2R4GB~3004GB analog output terminals
Inverter
Near-end of shield line is
grounded