Chapter 5 Detailed Function Introductions
123
Table 5-3-6 STEP Indication of number of steps of program running
Y3
Y2
Y1
DO
Steps of program
running
OFF
OFF
OFF
ON
T1
OFF
OFF
ON
OFF
T2
OFF
OFF
ON
ON
T3
OFF
ON
OFF
OFF
T4
OFF
ON
OFF
ON
T5
OFF
ON
ON
OFF
T6
OFF
ON
ON
ON
T7
ON
OFF
OFF
OFF
T8
ON
OFF
OFF
ON
T9
ON
OFF
ON
OFF
T10
ON
OFF
ON
ON
T11
ON
ON
OFF
OFF
T12
ON
ON
OFF
ON
T13
ON
ON
ON
OFF
T14
ON
ON
ON
ON
T15
P3.25 Cut-to-length reaching terminal output hold time
(3004GB and below models)
Setting range: 0.0 ~ 3.0s [1.0s]
Notes:
3004GB and below models: P3.25 is used to set this function, otherwise it is used for selection of output
function terminal of relay 2, please see the above description for details;
In P3.19, P3.24, set DO, relay 1 output is active when it is "fixed length reaching".
When P3.25 is set to 0: Cut-to-length reaching terminal output signal holds for a long term until the length is
cleared.
When P3.25 is not set to 0: value of P3.25 represents the terminal output signal hold time after the fixed
length reaches the set point.
P3.26 frequency reaching detection width
Setting range: 0.00 ~ 10.00 Hz [2.50 Hz]
Notes:
When the output frequency reaches the set frequency, the function adjusts its detection width. The adjustment
range is 0 ~ ± 10.00Hz of the set frequency. When the inverter's output frequency is within the positive and
negative detection width of the set frequency, specify terminal output active signal, as shown in Fig. 5-3-8.